AOUG36/48LMAS1
5. HIGH PRESSURE PROTECTION
During the compressor operation, when detect the condition of the following table value,
the protection function will be worked.
The operation condition varies according to the compressor speed.
The protection function is, the compressor speed is descreased 7 rps every 60 seconds.
When the outdoor unit discharge pressure sensor rises above 580.2 psi (4 MPa), the
compressor will stop.
04-35
AOUG36LMAS1
AOUG48LMAS1
226 °F
(108°C)
Operation value
Compressor frequency[rps]
Operation value[psi(MPa)]
Heating operation
rps
<= 90
rps
<= 20
20<
rps
<= 100
90<
rps
100<
HP>=500.38psi(3.45MPa)
HP>=507.63psi(3.50MPa)
HP>=478.62psi(3.30MPa)
HP>=449.62psi(3.10MPa)
HP>=471.37psi(3.25MPa)
HP>=478.62psi(3.30MPa)
HP>=449.62psi(3.10MPa)
HP>=420.61psi(2.90MPa)
Release value[psi(MPa)]
Compressor frequency[rps]
Operation value[psi(MPa)]
Cooling operation
rps
<= 90
rps
<= 20
20<
rps
<= 100
90<
HP>=500.38psi(3.45MPa)
HP>=551.14psi(3.80MPa)
HP>=478.62psi(3.30MPa)
HP>=471.37psi(3.25MPa)
HP>=522.14psi(3.60MPa)
HP>=449.62psi(3.10MPa)
Release value[psi(MPa)]
HP : Detected discharge pressure sensor value.
rps : Detected compressor frequency.
6. COMPRESSOR TEMPERATURE PROTECTION
Compressor temperature sensor is monitoring the compressor Temperature 1.
When the compressor temperature sensor detects higher than Temperature 1, the compressor
is stopped.
When 3 minutes has passed from the compressor stop and the compressor temperature sensor
detects lower than Temperature 2, protection is released and compressor will restart.
AOUG36/48LMAS1
Temperature 1 Temperature 2
176 °F
(80 °C)
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...