1-2 OUTDOOR UNIT DISPLAY (AOUG36,48LMAS1)
03-03
F
1
2
3
4
5
6
7
8
9
A
C
F
J
P
U
E
D
C
For MONITOR
(A and B)
Display mode
LED on:
LED off:
Blink:
(0.5s Light on
/ 0.5s Light off)
Number
of blinking: ( )
A: 10 times
C: 11 times
F: 12 times
J: 13 times
P: 14 times
U: 15 times
If an error occurs, the LED will light up to display the error location and the error code.
The error LED ashes quickly.
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
Blink
(High-speed)
LEDs A to F of MONITOR light up and display the error location. In the case of an overall
error, LEDs A to F of MONITOR do not light up.
Example) Coil error in indoor unit A
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
Blink
(High-speed)
Error code
In the event of an error
Error location display
While the error is occurring, brie y press SW1. The error code is displayed.
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
[A(10)]
1
Blink
(High-speed)
[A (10 times)]
Example) Coil error (Error code = 9A.1)
(9 times)
Error code display
Summary of Contents for AMUG24LMAS
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Page 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Page 105: ......
Page 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Page 146: ......
Page 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...