Trouble shooting 21 E41. 1
INDOOR UNIT Error Method:
Inlet air temp. Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Inlet air temp Sensor
Detective details:
When Inlet air temp. sensor open or shortage is detected
Forecast of Cause :
1. Connector defective connection 2. Sensor defective 3. Controller PCB defective
Check Point 2 : Remove connector and check Sensor resistance value
Sensor characteristics (Rough value)
If Sensor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if sensor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.5
35
8.0
30
10.0
12.5
15.8
20.1
25.2
33.6
Resistance Value (
)
25
20
15
10
5
0
Temperature (
95
86
77
68
59
50
41
32
Temperature (
°C)
°F)
3.5
4.3
5.3
50
45
40
122
113
104
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Corresponding connector
If the voltage does not appear, replace Controller PCB and set up the original address.
DC
Duct type
Cassette type
Compact Wall type
Wall type
Floor/Ceilling type
Room temp. Sensor (Black Wires)
CN8
Model Type
04-30
Resistance Value (
)
Temperature (
Temperature (
°C)
°F)
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......