Heat Ex.1 gas temp. Error
Heat Ex.1 gas temp. sensor (TH7)
Heat Ex.1 gas temp. sensor (TH7) for use as condenser
(4way valve1:Off, EEV1:Open) is detected abnormally-low to
High pressure saturated temp. for 4 minutes or more.
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A 6. 3
Error Code : 9 U / A 6
1. Heat Ex.1 gas temp. sensor (TH7) not installed correct position.
2. Heat Ex.1 gas temp. sensor (TH7) defective
3. 4-way valve1 (including a coil) defective
4. EEV1 (including a coil) defective
5. Main PCB defective
Trouble shooting 66 EA6. 3
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
Check Point 1 : Check the condition of Heat Ex.1 gas temp. sensor (TH7)
Check the condition of mounting of Heat Ex.1 gas temp. sensor (TH7).
Check Point 3 : Check the condition of 4-way valve1 coil
Check the condition of mounting of 4-way valve1 coil and 4-way valve2 coil.
OK
Check Point 2 : Check the Heat Ex.1 gas temp. sensor (TH7)
Check characteristics check. (Disconnect the Heat Ex.1 gas temp. sensor from PCB and check.)
* For the sensor characteristics, refer to the "Service Parts Information 25".
OK
Check Point 4 : Check the EEV
Check the condition of mounting of EEV1 coil.
Check the connector connection state of EEV1, EEV2, EEV3 coil.
OK
Check Point 6 : Replace 4-way valve1
1. Fully close the 3-way valve, and the refrigerant is recovered.2. 4-way valve1 is replaced.
3. Perform vacuuming of repaired outdoor unit thoroughly , and add the refrigerant
with the recovered amount.
4. Check if the error reoccurs on a test run.
OK
OK
Check Point 5 : Replace Main PCB
Check the appearance and condition of mounting of Main PCB.
>> If it is abnormal, replace Main PCB.
(When Main PCB is replaced, set up the original setting by Rotary, Dip, and Push SW.)
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-75
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......