LED101
Inverter Compressor Operation Indication
Low Noise Mode
Compressor Temperature Protection is stopped
Low Pressure Protection is stopped
High Pressure Protection is stopped
Discharge Temp. Protection is stopped
Defrost Operation
Oil Recovery Operation
Heating Mode (Mainly Heating)
Cooling Mode (Mainly Cooling)
Idling(stop)
Indication type
7 Segment LED Pattern
4-1-2 OUTDOOR UNIT DISPLAY
LED104
LED105
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" eak "C" ut
"L" OW "N" OISE
"SN" OW
Blinking
Description
POWER
LED101
ERROR
LED102
ON
ON
OFF
OFF
Snow Falling Protection Fan mode
"P" ROTECT "4"
ON
OFF
1 sec
1 sec
Peak Cut Mode
<Starting condition>
Discharge temp fixed value 239°F(115°C)
<Release condition>
3 minutes have elapsed and discharge temperature 176°F(80°C)
<Starting condition>
Compressor temp fixed value 239°F(115°C)
<Release condition>
3 minutes have elapsed and discharge temperature 176°F(80°C)
<Starting condition>
Low pressure 7psi (0.05MPa)
or low pressure 15psi (0.10MPa) continues for 10 mins
<Release condition>
3 minutes have elapsed and low pressure 25psi (0.17MPa)
<Starting condition>
High pressure 611psi(4.00MPa) or Pressure SW in operation
<Release condition>
5 minutes have elapsed and high pressure
509psi (3.50MPa)
and
Pressure SW release
Refer to Chapter 02.
(Outdoor unit operation control)
Refer to Chapter 02.
(Outdoor unit operation control)
Refer to Chapter 02.
(Outdoor unit operation control)
Refer to Chapter 02.
(Outdoor unit operation control)
04-02
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......