Protective function
Detect
device
Operation
Cool Heat
Display
2-9-10 Fan Motor, Motor Driver abnormal stop protection
Start condition
Release condition
Embeded
device
Embeded
device
Embeded
device
E97. 1
1. When the outdoor fan rotation speed is
less than 100rpm in 20seconds after
fan motor starts.
2. After the fan motor restarts, and when
the condition 1 is repeated consecutively
4 times.
Fan Motor lock
protection stop
Fan Motor
temperature
protection stop
E97. 5
1. When the FAN motor failed the operation
more than 470rpm.
2. After the fan motor restarts, and if the fan
motor cannot operate at 470rpm or more,
or the condition 1 is repeated
consecutively 3 times within 60 minutes.
Error reset (push
button SW)
executed after
power turned on
Fan Motor and
Compressor Stop
Error indication
Fan Motor driver
protection stop
E97. 9
When the Driver PCB detects the following
abnormalities,
Driver PCB defective, Fan motor defective
(short circuit), Main PCB defective (DC
output abnormal), lose connection, or
Disconnecting wire.
Protective function
Detect device
Operation
Cool Heat Display
2-9-11 EEV Coil abnormal Stop
Indoor unit
Controller
PCB EEV
drive Circuit
Error on IU.
LED blinks
Operation 5 times
Timer 2 times
When the EEV
coil drive circuit
is open circuit
Drive circuit detects
normal condition
and Power reset
System Stop
Error indication
“I.U Coil 1 Error”
Indoor unit EEV
coil abnormal
Stop
Outdoot unit
EEV coil 1,2,3
abnormal Stop
Start condition
Release condition
Outdoor unit
Controller
PCB EEV
drive Circuit
E9A“X“
Coil No, “X“
System Stop
Error indication
“CoiX1 Error”
Coil No, “X“
Error on OU.
7-Seg display
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......