01-14
Check Contents Check items
Checking method
Judgement
Present Status
Ref. circuit : Name _________________, Ref. address ________(select from 00 to 99)
Design value
Check status
Transmission line
connection
confirmation
check
Cooling status
Operate all Indoor
Units under Test
- run
Cooling Mode by
using Commissioning
Function of Service
Tool
Judgment Point during
test - mode cooling :
For Indoor Unit
- Thermistor value
(TH21 - TH22)14.4 F 8
(Yes / No)
For RB Unit
- SV status
SVB1 & SVS must ON
(Yes / No)
IU
RB
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
IU add _____ (RB add ____)
Yes /
No
Yes /
No
Check Contents
Check items
Checking method
Judgement
Present Status
Ref. circuit : Name _________________, Ref. address ________(select from 00 to 99)
Design value
Check status
Transmission line
connection
confirmation
Heating status
Switching the operation of IU
from cool to heat in order of RB
group number by using,
Control function of Service Tool
Judgment Point after
switching IU mode from
cool to heat in order of
RB group number:
For Indoor Unit
- Thermistor value
(TH24 > TH21)
(Yes / No)
IU
IU add _____ (RB add ____)
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
IU add _____ (RB add ____ )
Y e s
/
N o
1-3-4 Transmission line connection check sheet
Note: The following check method by using test-run is necessary for checking of incorrect transmission wire connection.
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......