01-15
Check Contents
Judgement
Present Status
Refrigerant Circuit : Name _________________, Address ________(00 99)
Conducted by
Service Tool
Degree of sub-cool at OU sub - cooler side should be,
(2 C Tshe 5 C).And,
Pulse value EEV3 should be,
Yes / No
Discharge refrigerant pressure should be,
363psi Pd 479psi(
Yes / No
Suction refrigerant pressure should be,
102psi Ps 174psi(
Yes / No
Discharge refrigerant temp. should be,
Discharge refrigerant superheat should be,
Yes / No
IU refg. superheat should be,
RB group SV (SBS & SVB1) should be ON AND
Pulse value IU EEV should be, EEV 1000P
Yes / No
Ps between Master & Slave OUs should be,
( Ps 29psi(0.2Mpa))
Yes / No
Air temperature of each RB group IU should be,
Tair c ooling
>
14.4 F(8 C)
Yes / No
No water fall from IU
No abnormal noise from IU
Yes / No
2.5MPa Pd 3.3MPa)
0.7MPa Ps 1.2MPa)
EEV3 400P
F( C)
F( C)
F( C)
F( C)
F( C)
F( C)
F( C)
F( C)
F( C)
F( C)
F( C)
( Tshd >18 F(10 C)
Tsc
EEV3 P
Pd Psi(MPa)
Ps Psi(MPa)
Td
Tshd
Tshe
SBS & SVB1 ON
IU EEV P
Ps Psi(MPa)
Tair c ooling
Tsc = Saturated liquid temperature of HPS - TH5
Tshd = TH1- Saturated liquid temperature of HPS
Tshe = TH24 - TH22
Tair c ooling = TH21 - Outlet Air temperature
Td = TH1
Pd = HPS
Ps = LPS
Reference mark of Service tool
Check Contents
Judgement
Present Status
Refrigerant Circuit : Name _________________, Address ________(00 99)
Test-run operation
Heating mode
Conducted by
Service Tool
Discharge refrigerant pressure should be,
Suction refrigerant pressure should be,
Discharge refrigerant temperature should be,
Discharge refrigerant superheat should be,
Degree of sub cool (at IU side) should be,
7.2 F 12.6 F
RB group SV (SBD1 & SVB2) should be ON
Refrigerant superheat (at OU side) should be,
Pd between Master & Slave OUs should be,
T
OUHE
at each OU connected in series should be,
Air temperature of each RB group IU should be,
363psi Pd 479psi (2.5MPa Pd 3.3MPa)
44psi Ps 174psi (0.3MPa Ps 1.2MPa)
Td 212 F (100 C) AND
Tshd > 18 F(10 C)
Tsc 7 ) AND
(4
3.6 F Tshe1& Tshe2 9 F(2 C Tshe1& Tshe2 5 C)
T
OUHE
>9 F(5 C)
Ps 29psi (0.2MPa))
Tair heating
>
27 F (15 C)
Tsc = Saturated liquid temperature of HPS - TH22
Tshd = TH1- Saturated liquid temperature of HPS
Tshe1 = TH7 - Saturated vapor temperature of LPS
Tair heating = TH21 - Outlet Air temperature
Reference mark of Service tool
Yes / No
Yes / No
Yes /
No
Yes / No
Yes / No
Yes / No
Yes / No
Tsc
Pd Psi(MPa)
Ps Psi(MPa)
Td
Tshd
Tshe
SVD1 & SVB2 ON
Ps Psi(MPa)
Tair heating
T
OUHE
Tshe2 = TH8 - Saturated vapor temperature of LPS
T = TH4 - TH9
OUHE 1
T = TH4 - TH10
OUHE 2
Test-run operation
Cooling mode
1-3-5 Operation check sheet
Td 212 F(100 C).And,
(3.6 F Tshe 9 F)
9 F TSC 36 F(5 C Tsc 20 C) AND
Tsc
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......