1-2 Check Items Before Power ON
01-03
Check Item
Check contents
Judgement
Present Status
Ref. circuit name: _________________
Power
Source
Outdoor
Unit
Power supply
3 / 3W / (208-230V 10%) / 60Hz
Circuit Breaker Size (A)
For AJUA72G : 45A
For AJUA90G / 120G : 55A
Master (AJUA ___G) :_____(A)
Slave-1(AJUA ___G) :_____(A)
Slave-2(AJUA ___G) :_____(A)
Leakage current : 100mA, 0.1 sec or less
Yes / No
Power Line Wire Size (mm
2
)
Check the breaker capacity vs. wire size
Master: ______ (AWG)
Slave-1: ______ (AWG)
Slave-2: ______ (AWG)
Power line Wiring
Note: One Outdoor Unit must have
one individual Circuit Breaker
Complied
Not complied
* Note: Regulation of wire size and circuit breaker differs from each locality, please refers in accordance with local rule
Check Item
Check contents
Judgement
Present Status
Ref. circuit name: _________________
Power
Source
Indoor
Unit &
RB Unit
Power supply
1
Circuit Breaker Size (A)
(Check, Leakage current vs.
number of IUs & RB units)
20A breaker for one circuit
Leakage current as follows:
No. of units vs. leakage current:
30mA for number of unit 44 units
100mA for 45 numberr of units 128 units
(Units means Indoor unit + RB unit)
Note:
MCA for total connected units (IU + RB) less
than 15A for 20A breaker capacity
MCA means, minimum circuit ampere
Circuit number -1
Breaker capacity: _______ (A)
Nos. of Connected units: ______ (IU+RB)
Circuit number -2
Breaker capacity: ______ (A)
Nos. of connected units: _______ (IU+RB)
Circuit number -3
Breaker capacity: _______ (A)
Nos. of Connected units: _______ (IU+RB)
Power line wire size
Check the breaker capacity vs. wire size
________ (AWG)
Example for one circuit
Complied
Not complied
* Note: Regulation of wire size and circuit breaker differs from each locality, please refers in accordance with local rule
1-2-1 Power source Inspection sheet
Example :
/ (208-230V 10%) / 60Hz
60Hz 230V
Circut breaker Circuit breaker
Earth lekage Over current
For (IU + RB units)
19 units
Power line wiring
1 2W
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......