Under The heat exchanger capacity is controlled using the 4WV, fan, and EEV according to the target high and low pressures.
The method for changing the capacity of the heat exchanger differs depending on the operation mode.
2-5-1 Operation mode selection and controlling
2-5 HEAT EXCHANGER CAPACITY CONTROL
System demand Heat-Ex conditions Controling device Control target
Cooling Condensor Fan Motor + 4WV (ON/OFF) +EEV Target High pressure
Heating Evaporator Fan Motor (Max rpm) + 4WV (ON) +EEV Maximum control
Cooling main Condensor Fan Motor + 4WV (ON/OFF) + EEV Target High / Low pressure
Heating main Evaporator Fan Motor + 4WV (ON) + EEV Target High / Low pressure
(1) Cooling (In case of 3 outdoor units connection)
Heat Exchanger condition: Condensor
- 4WV ON / OFF (Dpending on HEX capacity shift)
Fan speed Controlling range
- 0 to 500 rpm Only one HEX in use
- 300 to 500 rpm During HEX capacity shift
- Over 500 rpm Full of Heat-Ex capacity
Heat Exchanger capacity shift controlling
- Increas: Upper HEX has a priority in usage condition.
(No available Upper HEX, Lower HEX use)
- Decrease: Lower HEX has a priority in stop condition.
880
500
300
0
Number of Condensor
1 2 3 4 5 6
Fan Speed
(rpm)
Target High pressure > Operating High Pressure
Target High pressure < Operating High Pressure
(2) Heating
Heat Exchanger condition: Evaporator
- 4WV ON state
Fan speed Controlling range
- Maximum speed
Heat Exchanger capacity shift controlling
- Use all of available HEXs (Maximum capacity)
880 (920)
0
Number of Evaporator
Maximum number of HEX available in use
Fan Speed
(rpm)
2-5-2 Capacity control
(3) Cooling Main / Heating Main (In case of 3 outdoor units connection)
Heat Exchanger condition: Depending on the difference between operating pressure and the Target High pressure and the Target Low pressure.
Fan speed controlling: Depending on the condition of HEX (Condensor / Evaporator)
Heat Exchanger capacity shift controlling:
- Increas: Upper HEX has a priority in usage condition.
(No available Upper HEX, Lower HEX use)
- Decrease: Lower HEX has a priority in stop condition.
880
500
300
0
Number of Evaporator
6 5 4 3 2 1 1 2 3 4 5 6
Fan Speed
(rpm)
Number of Condensor
Master
r
HEX1
HEX2
Slave1
r
Slave2
r
The heat exchanger is operated at maximum efficiency by using each outdoor unit. (Max. 6 Heat exchanger can be used)
HEX1
HEX2
HEX1
HEX2
Heating Main
Cooling Main
(920)
(500)
(300)
(920)
(500)
(300)
( ) :L-Chassis
( ) :L-Chassis
( ) :L-Chassis
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......