![FujiFilm PXG4 Operation Manuals Download Page 81](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483081.webp)
– 80 –
8
Chapter
Remote SV Zero Adjustment
,
Remote SV Span Adjustment
This function adjusts remote SV zero/span.
Use this function to match zero/span to an output gauge.
• Range: -50.0% to 50.0% FS (zero/span)
Zero/span adjustments for input in the 1-5V range are as
follows:
Adjusting Remote SV Zero/Span
The following steps explain how to adjust remote SV zero/
span by using a zero deviance of -5% and a span deviance of
7% as an example.
1
Confirm the accuracy of the SV display by
checking the PV display when the mV generator
or dial resistor is set to 0 and 100%.
The zero display deviance is -5% and the span
display deviance is 7%.
Refer to
See "Remote SV (RSV) Pin Input Display" (p. 66) for more
information on confirming remote SV.
2
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh 6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
3
Set the input from the mV generator to 0%.
4
Press and hold the
key, then use the
keys to display rEM0 ("
rrr
rEEEEMMMM0000
").
RSV display
zero adjustment
span adjustment
input
100%
5V
1V
0%
5
Press the
key, then use the
keys to
select 5.0 when the bottom part of the display
begins to blink.
The zero display deviance is -5%, so the correction is
5.0%.
6
Press the
key to confirm the setting.
7
Set the input from the mV generator to 100%.
8
Press and hold the
key, then use the
keys to display rEMS ("
rrr
rEEEEMMMMSSSS
").
9
Press the
key, then use the
keys to
select -7.0 when the bottom part of the display
begins to blink.
The span display deviance is 7%, so the correction is
-7.0%.
10
Press the
key to confirm the setting.
11
Press the
key to return to the operation mode
PV/SV display.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Page 157: ...156 MEMO 17 Chapter...