– 79 –
8
Chapter
Cold Junction Compensation
This is the procedure for turning cold junction compensation
on or off when using input from a thermocouple sensor.
This setting should be left "ON" during normal operation. It
should oly be turned off when cold junction compensation is
being performed externally or you wish to record temperature
differences.
• Range on
: Cold junction compensation on
oFF : Cold junction compensation off
Setting Cold Junction Compensation
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh1111
"), then use the
keys to display SET ("
SSS
SEEEETTTT CCCChhhh6666
").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
2
Press and hold the
key, then use the
keys to display rCJ ("
rrr
rCCCCJJJJ
").
3
Press the
key, then use the
keys to
select "oFF" when the bottom part of the display
begins to blink.
Cold junction compensation is turned off.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV display.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Page 157: ...156 MEMO 17 Chapter...