![FujiFilm PXG4 Operation Manuals Download Page 153](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483153.webp)
– 152 –
16
Chapter
Troubleshooting
When symptoms thought to be damage occur, first check that there are no problems with the model purchased, wiring, or
parameter settings. The following lists examples of frequent problems and their solutions.
Trouble
Cause
Solution
Reference
Ch
Cannot communicate
with the host
Parity does not agree.
Make the parity on the host and the unit the same.
Ch9
Communication speed does not agree.
Make the communication speed on the host and
the unit the same.
Parameters you want
to view do not appear
Display mask is set.
Check the DSP settings.
Ch12
A password is set.
Release the password with Super PASS.
Ch11
Control output is not
output even with the
power turned on
Soft start is set.
Check the soft start settings.
Ch6
The ramp/soak settings have the output turned OFF.
Check the ramp/soak settings.
Ch4
Standby mode is on.
Check the output settings during standby mode.
Ch6
Manual mode cannot
be changed
Manual mode is not assigned to the USER key.
Check the USER key assignments.
Ch7
The DI function is not set to manual mode.
Check the DI function settings.
Keys do not work
Key lock is set to ON.
Check the key lock settings.
Ch1
SV limit value is set.
Check the SV limit value settings.
Ch2
The USER key settings have changed.
Check the USER key settings.
Ch7
Channel parameters
cannot be displayed
Password is incorrect.
Release the password with Super PASS.
Ch11
Forgot the password.
Power will not turn on
Equipment with 24V specification was connected to
AC 100V or more.
Please request repair.
—
SV blinks when
power is turned on
Standby is turned ON.
Release standby.
Ch1
Ramp/soak status is “END”.
Change the ramp/soak settings.
Ch1
ALMF is set.
Check the ALMF settings.
Ch13
Control does not start
even if power is
turned on
STMD mode is set to manual output.
Check the STMD settings.
Ch7
Cannot perform valve
control correctly
The valve is not correctly connected.
Check the valve connections.
Ch10
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...