![FujiFilm PXG4 Operation Manuals Download Page 26](http://html1.mh-extra.com/html/fujifilm/pxg4/pxg4_operation-manuals_2342483026.webp)
– 25 –
3
Chapter
Ramp/Soak Command
Switches between ramp/soak states.
The following three conditions are possible.
• "
oFF
" (stop) : The ramp/soak is stopped.
• "
rUn
" (run) : The ramp/soak starts.
• "
hLd
" (hold) : The ramp/soak holds. To release the hold,
select "
rUn
" again.
The parameter information also changes automatically
depending on the ramp/soak state.
• “
GS
” (during guaranty soak): PV exceeds the range for
guaranty soak when guaranty soak is on.
• “
End
” (end) : Ramp/soak ends.
Activating the Ramp/Soak Command
Refer to
See "Chapter 6 Ramp/Soak Parameters" (p. 53) for more information
on ramp/soak.
1
Press and hold the
key to display the channel
menu of the setting mode, then use the
keys to display "
ooo
oPPPPEEEE CCCChhhh 1111
".
Refer to
See p. 23 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key, then use the
keys to display PrG ("
PPP
PrrrrGGGG
").
3
Press the
key, then use the
keys to
display "
rrr
rUUUUnnnn
" when the bottom section of the
screen begins to blink.
4
Press the
key to confirm the setting.
The ramp/soak function will begin.
5
Press the
key to return to the PV/SV display
of the operation mode.
Auto-tuning
Running auto-tuning automatically sets the optimal PID.
• Range oFF : Stop/Finish
on
: Auto-tuning (normal type) starts
Lo
: Auto-tuning (low PV type) starts
There are two types of auto-tuning.
Running Auto-tuning
Normal type
Requests PID and starts ON/OFF
operation with SV as the baseline.
Low PV type
Requests PID and ON/OFF operation at
a baseline of SV-10%. Use this setting if
you are trying to prevent overshoot.
Caution
ON/OFF control is performed during auto-tuning, so SV may
be overshot. If you are trying to minimize overshooting, use
low PV auto-tuning.
Refer to
See "Control Methods" (p. 101) for more about auto-tuning.
1
Press and hold the
key to display the channel
menu of the setting mode, then use the
keys to display "
ooo
oPPPPEEEE CCCChhhh 1111
".
Refer to
See p. 23 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key, then use the
keys to select AT ("
AAA
ATTTT
").
Select the type of auto-tuning.
3
Press the
key, then use the
keys to
display "
ooo
onnnn
" when the bottom part of the display
begins to blink.
This selects normal auto-tuning.
4
Press the
key to confirm the setting.
Auto-tuning begins.
5
Press the
key to return to the PV/SV display
of the operation mode.
A decimal point will blink in the bottom
of the display during auto-tuning.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...