88
PB
TROUBLESHOOTING
Diagnostic Codes
No. Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display
status and during blinking, ON
0.5s and OFF 0.5s
Power
Indicator
Cool
Indica
-
tor
Heating
Indicator
Yellow
Indicator
Red Indi-
cator
Green
Indicator
30
module high
temperature
protection
P8
OFF 3s
and blink
19 times
During cooling operation,
compressor will stop while
indoor fan will operate;
During heating operation,
the complete unit will stop
After the complete unit is
de-energized for 20mins,
check whether the thermal
grease on IPM Module of
outdoor control panel AP is
sufficient and whether the
radiator is inserted tightly.
If no faults found, replace
control panel AP1
31
decrease
frequency
due to high
temperature
resistant
during
heating
operation
H0
OFF 3s
and blink
10 times
All loads operate normally,
while
operation frequency for
compressor is decreased
Refer to the malfunction
analysis (overload, high
temperature resistant)
32
static
dedusting
protection
H2
OFF 3s
and blink
twice
33
overload
protection
for com
-
pressor
H3
OFF 3s
and blink
3 times
OFF 1s
and blink
8 times
During cooling and drying
operation, compressor will
stop while indoor fan will
operate; During heating
operation, the complete unit
will stop operation.
1.Wiring terminal OVC-
COMP
is loosened. In normal
state, the resistance for
this terminal should be less
than 1ohm.
2.Refer to the malfunction
analysis ( discharge protec
-
tion, overload)
34
system is
abnormal
H4
OFF
3s and
blink 4
times
OFF 1s
and blink
6 times
During cooling and drying
operation, compressor will
stop while indoor fan will
operate; During heating
operation, the complete unit
will stop operation.
Refer to the malfunction
analysis (overload, high
temperature resistant)
35
IPM protec
-
tion
H5
OFF
3S and
blink 5
times
OFF 1s
and blink
4 times
During cooling and drying
operation, compressor will
stop while indoor fan will
operate; During heating
operation, the complete unit
will stop operation.
Refer to the malfunction
analysis (IPM protec
-
tion, loss of synchronism
protection and overcurrent
protection of phase current
for compressor.
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...