109
PB
Possible Causes
Discriminating Method (Air conditioner
Status)
Troubleshooting
Flow volume of valve is insufficient
The pressure of valves is much lower than
that stated in the specification
Open the valve completely
Malfunction of horizontal louver
Horizontal louver can’t swing
Refer to point 3 of maintenance method for
details
Malfunction of the IDU fan motor
The IDU fan motor can’t operate
Refer to troubleshooting for H6 for mainte
-
nance method in details
Malfunction of the ODU fan motor
The ODU fan motor can't operate
Refer to point 4 of maintenance method for
details
Malfunction of compressor
Compressor can't operate
Refer to point 5 of maintenance method for
details
Horizontal Louver Will Not Swing
Wrong wire connection, or poor connection Check the wiring status according to circuit
diagram
Connect wires according to wiring diagram
to make sure all wiring terminals are con
-
nected firmly
Stepping motor is damaged
Stepping motor can't operate
Repair or replace stepping motor
Main board is damaged
Others are all normal, while horizontal
louver can't operate
Replace the main board with the same
model
ODU Fan Moto Can’t Operate
Wrong wire connection, or poor connection Check the wiring status according to circuit
diagram
"Connect wires according to wiring dia
-
gram to
make sure all wiring terminals are con
-
nected firmly"
Capacity of the ODU fan motor is damaged
"Measure the capacity of fan capacitor with
an universal meter and find that the capac
-
ity is out of the deviation range indicated on
the nameplate of
fan capacitor."
Replace the capacity of fan
"Power voltage is a little low or
high"
"Use universal meter to measure the
power supply
voltage. The voltage is a little high or low"
Suggest to equip with voltage regulator
Motor of outdoor unit is damaged
"When unit is on, cooling/heating perfor
-
mance is bad and ODU compressor gener
-
ates a lot of
noise and heat."
Change compressor oil and refrigerant. If
no better, replace the compressor with a
new one
Compressor Can’t operate
Wrong wire connection, or poor connection Check the wiring status according to circuit
diagram
"Connect wires according to wiring dia
-
gram to make sure all wiring terminals are
connected
firmly"
TROUBLESHOOTING
Troubleshooting for normal Malfunction
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...