OPERATION
9-12k Sequence of Operation
Overheating Control
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating frequency limitation and prevent abnormal
high pressure. (The signal from the indoor unit must be divided as follows.)
1.Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 seconds from operation start.
2.Control in Each Zone
The heat exchange intermediate temperature of indoor unit controls the following.
Defrost Control
Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature is dependent
Reset zone
Up zone
Keep zone
Dropping zone
Stop zone
1.Conditions for Starting Defrost
The starting conditions must be made with the outdoor ambient air sensor (outdoor air temperature) and indoor coil sensor
2.Conditions for Canceling Defrost
Current indoor coil sensor (heat exchanger temperature) is between 39°F~72°F)
Heat exchanger
thermistor temperature
Compressor
Frequency
Fan
Electronic expansion
Four way valve
ON
valve opening
OFF
ON
OFF
ON
OFF
0Hz
5sec.
350pps
450pps
450pps
Initial opening
PI control
5sec.
50sec.
50sec.
600sec.
60sec.
on specific conditions being met or satisfied before releasing defrost.
(heat exchanger temperature). When the system is in heating operation for 6 minutes after the compressor is started or more than 45
minutes of accumulated time has passed since he start of operation or ending the defrost cycle
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...