83
PB
TROUBLESHOOTING
Diagnostic Codes
No. Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display
status and during blinking, ON
0.5s and OFF 0.5s
Power
Indicator
Cool
Indica
-
tor
Heating
Indicator
Yellow
Indicator
Red Indi-
cator
Green
Indicator
1
High
Pressure
Protectioon
Of System
E1
OFF 3s
and blink
once
During cooling and drying
operation, except indoor
fan operates, all loads stop
operation.
During heating operation,
the complete unit stops.
Possible reasons:
1.Refrigerant was super
-
abundant;
2.Poor heat exchange (in
-
cluding filth blockage of
heat exchanger and bad
radiating environment );
Ambient temperature is
too high.
2
Antifreezing
protection
E2
OFF 3s
and blink
twice
OFF 1 s
and blink
3 times
During cooling and drying
operation, compressor
and outdoor fan stop while
indoor fan operates.
1.Poor air-return in indoor
unit;
2.Fan speed is abnormal;
3.Evaporator is dirty.
3
In Defect of
refrigerant
F0
OFF 1 s
and blink
9 times
The Dual-8 Code Display
will show F0 and the com
-
plete unit stops.
1.In defect of refrigerant;
2.Indoor evaporator
temperature sensor works
abnormally;
3. The unit has been
plugged up somewhere.
4
High Dis
-
charge tem
-
peraature
protection of
compressor
E4
OFF 3s
and blink
4 times
OFF 1s
and blink
7 times
During cooling and drying
operation, compressor
and outdoor fan stop while
indoor fan operates. During
heating operation, all loads
stop.
Please refer to the mal-
function analysis (discharge
protection, overload).
5
Overcurrent
protection
E5
OFF 3s
and blink
6 times
OFF 1s
and blink
5 times
During cooling operation,
compressor stops while
indoor fan motor operates.
During heating operation,
the complete unit stops.
1. Supply voltage is
unstable;
2. Supply voltage is too low
andload is too high;
3. Evaporator is dirty.
6
Commu-
nication
malfunction
E6
OFF 3s
and blink
6 times
Always on
During cooling opera
-
tion, compressor stops
while indoor fan motor
operates. During heating
operation, the complete
unit stops.
Refer to the correspond
-
ing malfunction analysis.
7
High
temperature
resistant
prtoection
E8
OFF 3s
and blink
8 times
OFF 1s
and blink
6 times
During cooling operation:
compressor will stop while
indoor fan will operate.
During heating operation,
the complete unit stops.
Refer to the malfunction
analysis (overload, high
temperature resistant).
8
EEPROM
malfunction
EE
OFF 3s
and blink
15 times
OFF 1s
and blink
11 times
During cooling and drying
operation, compressor will
stop while indoor fan will
operate; During heating
operation, the complete unit
will stop
Replace outdoor control
panel AP1
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...