44
PB
OPERATION
36k Sequence of Operation
136
144
126
131
136
144
208
217
230
Diagostic
code
Designation of Sensors
Faults
F1
Indoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for
successive 5 seconds
F2
Indoor tube temperature
The sensor is dected to be open-circuited or short-circuited for suc
-
cesive 5 seconds
F3
Outdoor ambient temperature The sensor is detected to be open-circuited or short-circuited for
successive 30 seconds
F4
Outdoor tube temperature
The sensor is detected to be open-circuited or short circuited for
successive 30 seconds, and no detection is performed is performed
within 10 minutes after defrost begins
F5
Exhaust
After the compressor has operated for 3 minutes, the sensor is
detected to be open circuited or short circuited for 30 successive
seconds
F6
Overload
After the compresor has operated for 3 minutes, the sensor is
detected to be open circuited or short circuited for 30 successive
seconds.
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...