110
PB
Possible Causes
Discriminating Method (Air conditioner
Status)
Troubleshooting
Capacity of compressor is damaged
"Measure the capacity of fan capacitor with
an universal meter and find that the capac
-
ity is out of the deviation range indicated on
the nameplate of
fan capacitor."
Replace the compressor capacitor
"Power voltage is a little low or
high"
"Use universal meter to measure the
power supply
voltage. The voltage is a little high or low"
Suggest to equip with voltage regulator
Coil of compressor is burnt out
"Use universal meter to measure the
resistance
between compressor terminals and it's 0"
Repair or replace compressor
Cylinder of compressor is blocked
Compressor can't operate
Repair or replace compressor
Air Conditioner is Leaking
Drain pipe is blocked
Water leaking from indoor unit
"Eliminate the foreign objects inside the
drain
pipe"
Drain pipe is broken
Water leaking from drain pipe
Replace drain pipe
Wrapping is not tight
"Water leaking from the pipe connection
place of
indoor unit"
Wrap it again and bundle it tightly
Abnormal Sound and vibration
"When turn on or turn off the unit, the panel
and other parts will expand and there's
abnormal
sound"
There's the sound of "PAPA"
Normal phenomenon. Abnormal sound will
disappear after a few minutes.
"When turn on or turn off the unit, there's
abnormal sound due
to flow of refrigerant inside air
conditioner"
Water-running sound can be heard
Normal phenomenon. Abnormal sound will
disappear after a few minutes.
"Foreign objects inside the indoor
unit or there're parts touching together
inside the indoor unit"
There's abnormal sound fro indoor unit
"Remove foreign objects. Adjust all parts'
position of indoor unit, tighten screws and
stick damping plaster between connected
parts"
"Foreign objects inside the outdoor unit or
there're parts touching
together inside the outdoor unit"
There's abnormal sound fro outdoor unit
"Remove foreign objects. Adjust all parts'
position of outdoor unit, tighten screws and
stick damping plaster between connected
parts"
"Short circuit inside the magnetic
coil"
"During heating, the way valve has abnor
-
mal
electromagnetic sound"
Replace magnetic coil
Abnormal shake of compressor
Outdoor unit gives out abnormal sound
"Adjust the support foot mat of compres
-
sor,
tighten the bolts"
TROUBLESHOOTING
Troubleshooting for normal Malfunction
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...