No. Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display
status and during blinking, ON
0.5s and OFF 0.5s
Power
Indicator
Cool
Indica
-
tor
Heating
Indicator
Yellow
Indicator
Red Indi-
cator
Green
Indicator
13
indoor
evaporator
temperature
sensor is
open/ short
circuted
F2
OFF 3s
and blink
twice
AC stops operation once
reaches the setting tem
-
perature. Cooling, drying:
internal fan motor stops
operation while other loads
stop operation; heating: AC
stop operation
1.Loosening or bad contact
of Indoor
evaporator temp. sensor
and mainboard terminal.
2.Components on the
mainboard fall down leads
short circuit
3.Indoor evaporator temp.
sensor damaged.(check
temp. sensor value
chart for testing)
4.Mainboard damaged.
14
outdoor
ambient
temperature
sensor is
open/ short
circuted
F3
OFF 3s
and blink
3 times
OFF 1s
and blink
6 times
During cooling and drying
operating, compressor
stops while indoor fan
operates; During heating
operation, the complete unit
will stop operation
Outdoor temperature sen
-
sor hasnt’ been connected
well or
is damaged. Please check
it by referring to the resis
-
tance table for temperature
sensor)
15
outdoor
condenser
temperature
sensor is
open/ short
circuted
F4
OFF 3s
and blink
4 times
OFF 1s
and blink
5 times
During cooling and drying
operation, compressor
stops while indoor fan will
operate; During heating
operation, the complete unit
will stop operation.
Outdoor temperature sen
-
sor hasnt been connected
well or
is damaged. Please check
it by referring to the resis
-
tance table for temperature
sensor
16
outdoor
discharge
temperature
sensor is
open/ short
circuted
F5
OFF 3s
and blink
for 5
times
OFF 1S
and blink
7 times
During cooling and drying
operation, compressor
will sop after operating for
about 3 mins,
while indoor fan will
operate; During heating
operation, the complete unit
will stop after operating for
about 3 mins.
1. Outdoor temperature
sensor hasnt been con
-
nected well or is damaged.
Please check it by referring
to the resistance table for
temperature sensor
2. The head of temperature
sensor hasnt been inserted
into the copper tube
17
limit/
decrease
frequency
due to
overload
F6
OFF 3s
and blink
for 6
times
OFF 1s
and blink
3 times
All loads operate normally,
while
operation frequency for
compressor is decreased
Refer to the malfunction
analysis (overload, high
temperature resistant)
TROUBLESHOOTING
Diagnostic Codes
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...