No. Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual-8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display
status and during blinking, ON
0.5s and OFF 0.5s
Power
Indicator
Cool
Indica
-
tor
Heating
Indicator
Yellow
Indicator
Red Indi-
cator
Green
Indicator
18
decrease
frequency
due to over-
current
F8
OFF 3s
and blink
8 times
OFF 1s
and blink
once
All loads operate normally,
while
operation frequency for
compressor is decreased
The input supply voltage is
too low; System pressure is
too high and overload
19
decrease
frequency
due to
high air
discharge
F9
OFF 3s
and blink
9 times
OFF 1s
and blink
twice
All loads operate normally,
while
operation frequency for
compressor is decreased
Overload or temperature
is too high; refrigerant is
insufficent Malfunction of
electric expansion valve
(EKV)
20
limit/
decrease
frequency
due to anti-
freezing
FH
OFF 3s
and blink
2 times
OFF 3s
and blink
2 times
OFF 1s
and blink
4 times
All loads operate normally,
while operation frequency
for compressor is de
-
creased
Poor air-return in indoor
unit or fan speed is too low
21
voltage for
DC bus bar
is too high
high
PH
OFF 3s
and blink
11 times
OFF 1s
and blink
13 times
During cooling and drying
operation, compressor will
stop while indoor fan will
operate; During heating
operation, the complete unit
will stop operation.
1.Measure the voltage of
position L and N on wiring
board (XT), if the voltage is
higher than 265VAC, turn
on the unit after the supply
voltage is increased to the
normal range.
2.If the AC input is normal,
measure the voltage of
electrolytic capacitor C on
control panel (AP1), if its
normal, theres malfunc
-
tion for the circuit, please
replace the control panel
(AP1)
22
voltage of
DC bus- bar
is too low
PL
OFF 3s
and blink
21 times
OFF 1s
and blink
12 times
During cooling and drying
operation, compressor will
stop while indoor fan will
operate; During heating
operation, the complete unit
will stop
1.Measure the voltage of
position L and N on wiring
board (XT), if the voltage is
higher than 150VAC, turn
on the unit after the supply
voltage is increased to the
normal range.
2.If the AC input is normal,
measure the voltage of
electrolytic capacitor C on
control panel (AP1), if its
normal, there is a malfunc
-
tion for the circuit, replace
the control panel (AP1)
TROUBLESHOOTING
Diagnostic Codes
Summary of Contents for MRM09Y1J
Page 8: ...8 INTRODUCTION MWM09Y1J MWM12Y1J Figure 101 Indoor Units MWM18Y3J MWM24Y3J MWM36Y3J...
Page 37: ...37 OPERATION 18 24kSequenceofOperation...
Page 38: ...38 OPERATION 18 24k Sequence of Operation O o 0 C L A B C D 1 1 4...
Page 39: ...39 OPERATION 18 24k Sequence of Operation...
Page 40: ...40 OPERATION 18 24k Sequence of Operation...
Page 41: ...41 OPERATION 18 24k Sequence of Operation...
Page 47: ...47 INSTALLATION...
Page 48: ...48 INSTALLATION Installation Tools...
Page 95: ...95 TROUBLESHOOTING Malfunction of IDU Fan Motor U8 Service Manual No Start End...
Page 116: ...116 FIgure 901 PARTS CATALOG Indoor Unit MWM09Y1J MWM12Y1J MWM09Y1J MWM12Y1J...
Page 118: ...118 FIgure 902 PARTS CATALOG Indoor Unit MWM18Y3J MWM24Y3J...
Page 123: ...123 FIgure 904 PARTS CATALOG Outdoor Unit MRM09Y1J MRM12Y1J MRM09Y1J MRM12Y1J...
Page 126: ...126 PARTS CATALOG Outdoor Unit MRM18Y3J FIgure 905...
Page 128: ...128 PARTS CATALOG Outdoor Unit MRM24Y3J FIgure 906...