49
PB
TROUBLESHOOTING
Diagnostic Codes
Led Display
Error
Code
Power Timer
Running
1
2
3
Content
The root cause is may be one of the following
0
Normal
1
BLINK
ON
ON
The failure for temperature
sensor of outdoor coil
a. The outdoor temperature sensor loose.
b. The outdoor temperature sensor failed.
c. The indoor control board failed
2
BLINK
ON
OFF
Compressor exhaust
temperature sensor in
trouble
a. the compressor exhaust temperature sensor connect
loose.
b. the compressor exhaust temperature sensor failed.
c. the outdoor control board failed.
5
ON
BLINK
OFF
IPM module protection
a.The IPM board failed.
b.The outdoor fan is broken.
c.The outdoor fan motor failed
d.The outdoor fan has been blocked.
e.The condenser is dirty.
f.The outdoor unit has been installed below standards.
6
OFF
BLINK
OFF
AC voltage higher or lower
protection
a. the supply voltage is higher or lower than normal.
b. the inner supply voltage of the unit is higher or lower
than normal.
7
ON
ON
OFF
Communication failure
between the indoor unit
and outdoor unit
a.the communication cable connect loose.
b.the communication cable failed.
c.the connection between the filter board and the
outdoor control board is incorrect or loose.
d.the connection between the filter board and the
terminal is incorrect or loose.
e.the indoor control board failed.
f.the PFC board failed.
g.the power board failed.
h.the outdoor control board failed.
8
Current overload protection a.the fan motor runs abnormally.
b.the condensor and evaporator are dirty.
c.the air inlet and outlet is abnormal or obstructed.
9
Maximum current
protection
a.the outdoor control board is short circuited.
b.the drive board is short circuited.
c.ther components are short circuited.
10
ON
OFF
OFF
Communication trouble
between outdoor unit and
driver
a. the connection wires connector loose.
b.the outdoor board or drive board failed.
11
BLINK
OFF
OFF
Outdoor EEPROM in trouble
a.the EEPROM chip is loose;
b.the EEPROM chip inserted in the opposite direction.
c.the EEPROM chip failed.
12
Outdoor ambient
temperature too low
protection
Outdoor ambient temperature too low.
13
BLINK
OFF
ON
Compressor exhaust
temperature too high
protection
a.the compressor exhaust temperature sensor failed
b.the refrigerant chage is low.
14
ON
ON
BLINK
Outdoor ambient
temperature sensor in
trouble
a.the outdoor ambient temperature sensor connector
is loose.
b.the outdoor ambient temperature sensor failed.
c.the outdoor control board failed.
15
OFF
BLINK ON
Compressor shell
temperature too high
protection
a.the compressor exhaust temperature sensor
connector loose.
b.the refrigerant charge is low.
Summary of Contents for Floating Air Pro-Premiere FPHFW18A3A
Page 25: ...25 INSTALLATION Installation Dimension Diagram Figure 401 ...
Page 26: ...26 INSTALLATION Main Tools For Installation and Maintenance Figure 402 ...
Page 34: ...34 INSTALLATION Install Outdoor Unit Fig 431 ...
Page 35: ...35 INSTALLATION Outdoor Units ...
Page 40: ...40 MAINTENANCE Fig 501 ...
Page 59: ...59 TROUBLESHOOTING Error Code 13 Fig 708 Error Code 8 ...
Page 62: ...62 TROUBLESHOOTING Error Code 20 DC fan motor test point Fig 711 ...
Page 68: ...68 Fig 716 TROUBLESHOOTING Error Code 36 ...
Page 73: ...73 COMPONENTS TESTING Fan Motor ...
Page 87: ...87 WIRING DIAGRAMS Outdoor Units Figure 805 9 36K Outdoor Units ...