51
PB
TROUBLESHOOTING
Diagnostic Codes
LED Display
Error
Code
Power Timer
Running
1
2
3
Content
The root cause is may be one of the following
38
BLINK
BLINK
OFF
Indoor EEPROM failure
a. The EEPROM chip loose;
b. The indoor control board failed.
39
BLINK
BLINK ON
Indoor fan motor run
abnormally
a. There is something blocking the indoor fan motor.
b. The fan motor cord connector loose.
c. The fan motor has failed.
d. The indoor control board failed.
41
OFF
OFF
ON
The failure for Indoor
grounding protective
The indoor control board failed.
The failure is detected when the room temperature sensor broken or shorted over 5 sec.
The failure is detected when the temperature sensor of heater exchange broken or shorted over 5 sec.
The failure is detected when each setting data is not match after the EEPPOM self-check two times.
The failure is occur when the grounding signal is not detected after the appliance power ON.
Summary of Contents for Floating Air Pro-Premiere FPHFW18A3A
Page 25: ...25 INSTALLATION Installation Dimension Diagram Figure 401 ...
Page 26: ...26 INSTALLATION Main Tools For Installation and Maintenance Figure 402 ...
Page 34: ...34 INSTALLATION Install Outdoor Unit Fig 431 ...
Page 35: ...35 INSTALLATION Outdoor Units ...
Page 40: ...40 MAINTENANCE Fig 501 ...
Page 59: ...59 TROUBLESHOOTING Error Code 13 Fig 708 Error Code 8 ...
Page 62: ...62 TROUBLESHOOTING Error Code 20 DC fan motor test point Fig 711 ...
Page 68: ...68 Fig 716 TROUBLESHOOTING Error Code 36 ...
Page 73: ...73 COMPONENTS TESTING Fan Motor ...
Page 87: ...87 WIRING DIAGRAMS Outdoor Units Figure 805 9 36K Outdoor Units ...