TROUBLESHOOTING
Diagnostic Codes
Outdoor Unit
When the unit has the following trouble and the compressor stops running, The LED of outdoor control board will show the
error sequence automatically:
Diag
Code
Outdoor Failure Description
LED1
LED2
LED3
the root cause my be one of the following
Mark description: the lights flash every second for the following faults
Outdoor coil temperature sensor
faulted
ON
OFF
ON
a.the outdoor coil sensor connector loose.
b.the outdoor coil temperature sensor failed.
c.the outdoor control board failed.
Compressor exhaust temperature
sensor faulted
ON
OFF
OFF
a.the compressor exhaust temperature sensor
connector loose.
b.the compressor exhaust temperature sensor
failed.
c.the outdoor control board failed.
Communication failure between the
indoor unit and outdoor unit
OFF
OFF
BLINKS
a.the communication cable connector loose.
b.the communication cable failed.
c.the connectorion between the filter board and the
outdoor control board is incorrect or loose.
d.the connectorion between the filter board and
the terminal is incorrect or loose.
e.the indoor control board failed.
f.the PFC board failed.
g.the power board failed.
h.the outdoor control board failed.
Current overload protection
ON
BLINKS
OFF
a.the fan motor run abnormally.
b.the condensor and evaporator is dirty.
c.the air inlet and outlet is abnormall.
Maximum current protection
ON
BLINKS
ON
a.the outdoor control board is short circuited.
b.the drive board is short circuited.
c.the other components are short circuited.
Communication trouble between
outdoor unit and driver
OFF
ON
ON
a. the connection wires are loose.
b.the outdoor board or drive board failed.
Outdoor EEPROM faulted
ON
ON
ON
a.the EEPROM chip is loose.
b.the EEPROM chip inserted in wrong direction.
c. The EEPROM chip failed.
Compressor exhaust temperature
too high protection
OFF
BLINKS
ON
a.the compressor exhaust temperature sensor
failed.
b.the refrigerant of the unit is low.
Outdoor ambient temperature
sensor faulted
ON
ON
OFF
a.the outdoor ambient temperature sensor
connecter loose.
b.the outdoor ambient temperature sensor
failed.
c.the outdoor control board failed.
Compressor shell temperature too
high protection
OFF
ON
BLINKS
a.the compressor exhaust temperature sensor
connector loose.
b.the refrigerant of the unit is low.
Anti-freeze protection with cooling
or overload protection with heating in
indoor unit
OFF
BLINKS
BLINKS
a.the indoor coil temperature sensor connector
loose.
b.the indoor coil temperature sensor
failed
.
c.the indoor control board
failed
.
d. the refrigerant system is abnormal.
Summary of Contents for Floating Air Pro-Premiere FPHFW18A3A
Page 25: ...25 INSTALLATION Installation Dimension Diagram Figure 401 ...
Page 26: ...26 INSTALLATION Main Tools For Installation and Maintenance Figure 402 ...
Page 34: ...34 INSTALLATION Install Outdoor Unit Fig 431 ...
Page 35: ...35 INSTALLATION Outdoor Units ...
Page 40: ...40 MAINTENANCE Fig 501 ...
Page 59: ...59 TROUBLESHOOTING Error Code 13 Fig 708 Error Code 8 ...
Page 62: ...62 TROUBLESHOOTING Error Code 20 DC fan motor test point Fig 711 ...
Page 68: ...68 Fig 716 TROUBLESHOOTING Error Code 36 ...
Page 73: ...73 COMPONENTS TESTING Fan Motor ...
Page 87: ...87 WIRING DIAGRAMS Outdoor Units Figure 805 9 36K Outdoor Units ...