36
PB
INSTALLATION
Power and Wiring
Capacity size
Wire Diameter(AWG)
Condenser / Interconnecting Wire
Circuit Breaker Capacity Rating
9k-12k
14 AWG 600V / 14-4 AWG 600V THHN
15A
18k
12 AWG 600V / 14-4 AWG 600V THHN
20A
24-36K
10 AWG 600V / 14-4 AWG 600V THHN
30A
Fig. 435
Installation Instructions,
l
Power and Wiring
Connecting of the Cable
• Indoor Unit
Front panel
Terminal
(Inside)
Connect the power cord to the indoor unit by connecting
the wires to the terminals on the control board individually
in accordance with the outdoor unit connection.
Note: For some models, it is necessary to remove the cabinet to
connect to the indoor unit terminal.
��������Cablnet
• Outdoor Unit
1) Remove the cable cross board from the unit by loosenlng
the screw. Connect the wires to the termlnals on the control
board individually per circuit diagram posted on inside of
access door.
2) Secure the power cord onto the control
board with cable clamp.
3)
Reinstall the cable cross board to the original position
with the screw.
4) Use a recognized circuit breaker between the power
source and the unit. A dlsconnecUng device to adequately
disconnect all supply lines must be fitted.
Caution:
Indoor unit
Chassis
Outdoor unit
Fig. 434
1. Never fail to have an individual power circuit specifically for the air conditioner.
2. Always refer to the circuit diagram posted on Iha inside of the access door for wiring.
3. Confirm that the cable thickness is as specified in the power source specification.
4.
Check the wires and make sure that they are all tightly fastened after cable connection.
5.
Be sure to install an earth leakage circuit breaker in wet or moist areas.
Cable Specifications
Summary of Contents for Floating Air Pro-Premiere FPHFW18A3A
Page 25: ...25 INSTALLATION Installation Dimension Diagram Figure 401 ...
Page 26: ...26 INSTALLATION Main Tools For Installation and Maintenance Figure 402 ...
Page 34: ...34 INSTALLATION Install Outdoor Unit Fig 431 ...
Page 35: ...35 INSTALLATION Outdoor Units ...
Page 40: ...40 MAINTENANCE Fig 501 ...
Page 59: ...59 TROUBLESHOOTING Error Code 13 Fig 708 Error Code 8 ...
Page 62: ...62 TROUBLESHOOTING Error Code 20 DC fan motor test point Fig 711 ...
Page 68: ...68 Fig 716 TROUBLESHOOTING Error Code 36 ...
Page 73: ...73 COMPONENTS TESTING Fan Motor ...
Page 87: ...87 WIRING DIAGRAMS Outdoor Units Figure 805 9 36K Outdoor Units ...