56
PB
TROUBLESHOOTING
Error Code 39-DC FAN
Error code 39
Indoor fan motor trouble
Set the air conditioner
operate in fan mode
Is indoor fan motor
running?
Does fan motor
stop following the
remote controller
order?
Check the connector of
indoor motor connected
tightly or not
Check the each pin to
“GND”pin shorted or not
Indoor control board
faulty and replace it
DC Fan
Replace the indoor
fan motor
With power on check
“Vdc”pin to “GND”pin
310Vdc or not;
“Vcc”pin to “GND”pin
15V or not
Yes
Yes
No
No
No
No
Yes
Yes
Fig. 703
DC Fan Test Points
Fig. 704