50
PB
TROUBLESHOOTING
Diagnostic Codes
LED Display
Error
Code
Power Timer
Running
1
2
3
Content
The root cause is may be one of the following
16
ON
OFF
ON
Anti-freeze protection
with cooling or overload
protection with heating in
a.the indoor coil temperature sensor connector loose.
b.the indoor coil temperature sensor failed.
c.the indoor control board failed.
d. the refrigerant system is abnormal.
17
OFF
ON
OFF
PFC protection
a.the PFC failed.
b.the outdoor drive board failed.
18
OFF
ON
ON
DC compressor start
failure
a.the outdoor drive board failed.
b.the compressor failed.
19
OFF
ON
BLINK
Compressor drive in
trouble
a.the outdoor drive board failed.
b.the compressor failed.
c. the outdoor control board failed.
20
ON
OFF
BLINK
Outdoor fan motor locked
rotor protection
a.the connection of the outdoor fan motor is loose.
b.there are something blocking the outdoor fan.
c.the fan motor failed.
d.the outdoor control board failed.
21
OFF
OFF
BLINK
Outdoor coil anti-overload
protection with cooling
a.the refrigerant charge is exxcessive.
b.the outdoor fan motor failed.
c.the outdoor fan is broken.
d.the condensor is dirty.
e.the air inlet and air outlet of the indoor unit and the
outdoor unit are abnormal.
22
Compressor pre heating
process
it is normal mode in cold weather
23
Expansion valve A tube
(thin) sensor fault
1. The wiring of the sensor for the expansion valve A
(thin tube) connect loose;
2. The sensor for the expansion A(thin tube) has failure;
3. The sampling circuit is abnormal.
24
Outdoor board chip failure.
a.Using the wrong drive board;
b.Using the wrong compressor.
26
Overheated outdoor
radiator
a. Radiator sensor fails.
b. Detection circuit of the sensor on the control panel
fails.
27
Protection against too high
system pressure
a. The pressure switch fails.
b. The pressure detection switch on the control panel
fails.
c. The measured value of system pressure exceeds the
limit.
33
ON
BLINK BLINK
Indoor room temperature
sensor failure.
a. The indoor room temperature sensor loose;
b. The indoor room temperature sensor is failure;
c. The indoor control board is failure.
34
OFF
BLINK BLINK
Indoor coil temperature
sensor failure.
d. The indoor coil temperature sensor loose.
e. The indoor coil temperature sensor failed.
f. The indoor control board failed.
36
BLINK
ON
BLINK
Communication failure
between the indoor unit
and outdoor unit
a.the communication cable connector loose.
b.the communication cable failed.
c.the connection between the filter board and the
outdoor control board is incorrect or loose.
d.the connection between the filter board and the
terminal is incorrect or loose.
e.the indoor control board failed.
f.the PFC board failed.
g.the power board failed.
h.the outdoor control board failed.
Summary of Contents for Floating Air Pro-Premiere FPHFW18A3A
Page 25: ...25 INSTALLATION Installation Dimension Diagram Figure 401 ...
Page 26: ...26 INSTALLATION Main Tools For Installation and Maintenance Figure 402 ...
Page 34: ...34 INSTALLATION Install Outdoor Unit Fig 431 ...
Page 35: ...35 INSTALLATION Outdoor Units ...
Page 40: ...40 MAINTENANCE Fig 501 ...
Page 59: ...59 TROUBLESHOOTING Error Code 13 Fig 708 Error Code 8 ...
Page 62: ...62 TROUBLESHOOTING Error Code 20 DC fan motor test point Fig 711 ...
Page 68: ...68 Fig 716 TROUBLESHOOTING Error Code 36 ...
Page 73: ...73 COMPONENTS TESTING Fan Motor ...
Page 87: ...87 WIRING DIAGRAMS Outdoor Units Figure 805 9 36K Outdoor Units ...