SPECIFICATIONS
54
Environmental
Ambient Operating Temp
-5 ° F to 140 °F (-20 °C to 60 °C)
Ambient Storage Temp
-5 ° F to 158 °F (-20 °C to 70 °C)
Relative Humidity
5% to 95% non-condensing
Motor Protection
Adjustment/Description
Default Setting
Overload Current Setting Range
1-135A, up to 1000A with external CTs
1.0 A
Overload Trip Class
Adjustable: 5-30
10 - SMS, 5, SMS-RV
Overload Service Factor
Adjustable: 1.00-2.00
1.15
Under Power (Dry Run)
On/Off/Alarm, adjustable: 1-99% of nominal
On/65%
Over Power
On/Off/Alarm, adjustable: 101-200% of nominal
On/125%
Under Voltage
On/Off/Alarm, adjustable: 80-99% of nominal
On/90%
Over Voltage
On/Off/Alarm, adjustable: 101-125% of nominal
On/110%
Voltage Phase Loss
Always On
On/Trips if below 60VAC
Ground Fault (UL 1053 Certified)
On/Off/Alarm, adjustable: 1-10 Amps
On/1A
Cycle Fault
On/Off, start limit adjustable: 2-100
On
SMARTSTART™ Protection
Adjustment/Description
Default Setting
Current Phase Unbalance
On/Off, adjustable: 1-50%
On / 5%
Locked Rotor/Stall
On/Off, trips if current exceeds 300% max amps
for 0.5 second
On
Out of Calibration
On/Off, trips after 10 seconds if max amps setting
is incorrect
Off
Max Time to Start
On/Off, regardless of max amps or I
2
T trip curve,
always trip at start if starting current is outside of
an acceptable range and still decreasing after ten
seconds.
Off
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...