COMMUNICATIONS
Modbus RTU Communication
48
515
RW
N
Soft Stop Voltage
Level
10 to 90; default = 70
Soft Stop Voltage Level percentage
516
RW
N
Soft Start Inside
Delta
0 - Disabled (default)
1 - Enabled
When enabled, allows for soft starting of motors equipped with
inside delta setup.
517
RW
N
Soft Start Motor PF
0.60 to 0.99; default = 0.80
multi = 0.01
Power Factor setting from Soft Start Motor Label
518
RW
N
D1 Type
0 - Normally Open (default)
1 - Normally Closed
D1 Contact Type Setting
519
RW
N
D1 Function
0 - Auto Run (default)
1 - Permissive 1
D1 Function Setting
520
RW
N
D2 Type
0 - Normally Open
1 - Normally Closed (default)
D2 Contact Type Setting
521
RW
N
D2 Function
0 - Shutdown (default)
1 - Permissive 2
D2 Function Setting
524
RW
N
D1/D2 Function
0 - Auto Run/Shutdown
(default)
1 - Fill Mode - Low/High Float
2 - Drain Mode - Low/High Float
Intended use for D1/D2 connection
526
RW
N
Limit Sw Delay
1 to 120; default = 30
Limit Switch Delay Time in seconds
527
RW
N
O1 Function
0 - General Fault (default)
1 - Shunt Trip
Output Relay O1 Function
528
RW
N
O2 Status Level
1 to 99; default = 60
Output Relay O2 Status Level Threshold
529
RW
N
Start Delay Enable
0 - Disabled (default)
1 - Enabled
Enables the Start Delay time period (below) for use in Hand
Mode and Auto Modes
530
RW
N
Start Delay Time
1 to 43,200; default = 1
Sets the Start Delay time period in seconds.
531
RW
N
Stop Delay Enable
0 - Disabled (default)
1 - Enabled
Enables the Stop Delay (in Auto Mode only)
532
RW
N
Stop Delay Time
1 to 43,200; default = 1
Sets the Stop Delay time period in seconds.
533
RW
N
Min Off Time Enable 0 - Disabled (default)
1 - Enabled
Enables the Minimum Off Time (for use with Hand Mode and
Auto Mode)
534
RW
N
Min Off Time
1 to 43,200; default = 1
Sets the Minimum Off Time in seconds
535
RW
N
Min Run Time Enable 0 - Disabled (default)
1 - Enabled
Enables the Minimum Run Time setting (below) for use in Auto
Mode only.
536
RW
N
Min Run Time
1 to 43,200; default = 1
Sets the Minimum Run Time in seconds
Mod
Bus R/W
RC
Address Name
Choices/Range
Description
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...