COMMUNICATIONS
Modbus RTU Communication
44
413
RW
N
Over Cur Level
100 to 200; default = 110
Over current level percentage. Percent of motor FLA/
SFA. If any phase current is greater than setting for Over
Current Delay, SMC faults/alarms.
414
RW
N
Over Cur Delay
1 to 120; default = 30
Over current delay, in seconds, to trip fault/alarm. Timer
is reset if the current drops below the motor Over Current
Level.
415
RW
N
Over Cur Reset
0 - Manual
1 - Automatic (default)
Over current reset method
416
RW
N
Over Cur Retry
1 to 10; default = 3
Over current automatic reset attempts
417
RW
N
Over Cur Reset
Delay
1 to 43,200; default = 900
Over current automatic reset delay time
418
RW
N
Unbl Cur Enable
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Current unbalance protection enable
419
RW
N
Unbl Cur Level
1 to 50; default = 5
Current unbalance level percentage
420
RW
N
Unbl Cur Delay
1 to 120; default = 10
Current unbalance delay to trip fault/alarm in seconds
421
RW
N
Unbl Cur Reset
0 - Manual
1 - Automatic (default)
Current Unbalance Reset Method
422
RW
N
Unbl Cur Retry
1 to 10; default = 3
Current unbalance automatic reset attempts
423
RW
N
Unbl Cur Rst Dly
1 to 43,200; default = 900
Current unbalance automatic reset delay in seconds
424
RW
N
Grnd Flt Enable
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Ground Fault Protection Enable
425
RW
N
Grnd Flt Level
1.0 to 10.0; default = 1.0
multi = 0.1
Ground Fault Level in amperes
426
RW
N
No Cur Enable
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
No Current Protection Enable
427
RW
N
Unexp Cur Enable 0 - Off (default)
1 - Fault and Alarm (default)
2 - Alarm Only
Unexpected Current Protection Enable
428
RW
N
Out Cal Enable
0 - Off (default)
1 - Fault and Alarm (default)
2 - Alarm Only
Out of Calibration Protection Enable
429
RW
N
Max Str Enable
0 - Off (default)
1 - Fault and Alarm (default)
2 - Alarm Only
Maximum Start Time Protection Enable
430
431
RW
N
Nominal Voltage
120.0 to 72,000; default =
208.0 multi = 0.1
Nominal Voltage setting
432
RW
N
Ovr Vlt Enable
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Overvoltage Protection Enable
433
RW
N
Ovr Vlt Level
101 to 125; default = 110
Overvoltage Level Percentage
434
RW
N
Ovr Vlt Delay
1 to 120; default = 10
Overvoltage Delay Time in seconds
435
RW
N
Ovr Vlt Reset
0 - Manual
1 - Automatic (default)
Overvoltage Reset Method
436
RW
N
Ovr Vlt Retry
1 to 10; default = 3
Overvoltage Automatic Reset Allowed Attempts
437
RW
N
Ovr Vlt Rst Dly
1 to 43,200; default = 900
Overvoltage Automatic Reset Delay in seconds
Mod
Bus R/W
RC
Address Name
Choices/Range
Description
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...