COMMUNICATIONS
Modbus RTU Communication
43
322
R
N
Phase A PF
-1.00 to 1.00 multi =
0.0 1
Phase A Power Factor
323
R
N
Phase B PF
-1.00 to 1.00 multi =
0.0 1
Phase B Power Factor
324
R
N
Phase C PF
-1.00 to 1.00 multi=
0.0 1
Phase C Power Factor
325
326
R
N
kWh
0 to 4,294,967,295
Accumulated kWh
327
R
N
Motor Insulation
0 to 65,535
Measured insulation resistance in kΩ
328
R
N
RTD Temperature -50 to 120
Temperature reading from RTD in °C
329
R
N
SubTemp
Temperature
0 to 150
Temperature reading from SubTemp signal in °C
330
R
N
SubTemp Status
0 - Good
1 - Searching
2 - Low Signal
3 - No Signal
4 - Off
Status of the SubTemp Receiver
331
Not Used
Not Used
Not Used
332
R
N
SCR Temperature 0 to 200
Temperature reading from SCR in °C
400
RW
N
Application
0 - Custom
1 - Submersible Pump
2 - Surface Pump
Motor application - Sets specific parameter presets based
on the selected pump application.
401
RW
N
FLA1
1.0 to 1000.0; default = 1;
multi = 0.1
FLA/SFA/high speed FLA
402
RW
N
FLA2
1.0 to 1000.0; default = 1;
multi = 0.1
Low-speed FLA
403
RW
N
OL Trip Class
0 - 4; default = 0/1
0 - 5 seconds or less
1 - 10 seconds or less
2 - 20 seconds or less
3 - 30 seconds or less
4 - Submersible Motor
Sets the overload trip class:
Reduced Voltage SMS default = 0
SMS (Surface Pump) default = 1
SMS (Submersible Pump) default = 4
404
RW
N
Service Factor
1.00 to 2.00; default = 1.15
multi = 0.01
Motor service factor
405
RW
N
OL Reset
0 - Manual
1 - Automatic (default)
Overload Reset Method
406
RW
N
OL Retry
1 to 10; default = 3
Overload automatic reset attempts
407
RW
N
OL Reset Delay
0 to 43,200; default = 900
Overload automatic reset delay (in seconds)
408
RW
N
OL Cooldown
Enable
0 - Disabled (default)
1 - Enabled
Overload cooldown run prevention enable
409
RW
N
OL Cooldown Time 1 to 43,200; default = 300
Overload cooldown time
410
RW
N
Lock Rotor Fault
0 - Off
1 - Fault (default)
Locked Rotor Enable
411
RW
N
Stall Enable
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Stall Enable
412
RW
N
Over Cur Enable
0 - Off
1 - Fault (default)
Over current protection enable
Mod
Bus R/W
RC
Address Name
Choices/Range
Description
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...