COMMUNICATIONS
Modbus RTU Communication
41
209
R
N
D1 Status
0 - Open
1 - Closed
Read this address for the status of dry input terminal D1.
210
R
N
D2 Status
0 - Open
1 - Closed
Read this address for the status of dry input terminal D2.
211
R
N
D3 Status
0 - Open
1 - Closed
Read this address for the status of dry input terminal D3.
212
R
N
D4 Status
0 - Open
1 - Closed
Read this address for the status of dry input terminal D4.
213
R
N
D5 Status
0 - Open
1 - Closed
Read this address for the status of dry input terminal D5.
214
R
N
V1/V2 Status
0 - De-energized
1 - Energized
Read this address for the status of wet input terminals V1/
V2.
215
R
N
V3/V4 Status
0 - De-energized
1 - Energized
Read this address for the status of wet input terminals
V3/V4.
216
R
N
O1 Status
0 - Open
1 - Closed
Read this address for the status of output Relay terminal
O1.
219
220
R
N
Date
MMDDYY
Read the system date. Only the 3 least significant bytes
are used. From least to most significant byte: year, day,
month (0x00MMDDYY).
221
222
R
N
Time
HHMMSS
Read the system time. Only the 3 least significant bytes
are used. From least to most significant byte: second,
hour, day (0x00HHMMSS).
227
R
N
Power Loss Count 0 to 4,294,967,295
Read the total number of times the unit was power-
cycled.
228
229
R
N
Motor Run Time
0 to 4,294,967,295
Read the accumulated amount of motor run time in sec
-
onds.
230
231
R
N
Power On Time
0 to 4,294,967,295
Read the accumulated system power-on time in seconds.
232
233
R
N
I/O Version
0 to 999,999
View the I/O device firmware version. Periods are implied
after 2 and 4 right decimal digits (10203 = v01.02.03).
234
235
R
N
Meter Version
0 to 999,999
View the Meter device firmware version. Periods are
implied after 2 and 4 right decimal digits (10203 =
v01.02.03).
236
237
R
N
Display Version
0 to 999,999
View the Display device firmware version. Periods are
implied after 2 and 4 right decimal digits (10203 =
v01.02.03).
238
239
R
N
I/O Boot Version
0 to 999,999
View the I/O boot loader version. Periods are implied
after 2 and 4 right decimal digits (10203 = v01.02.03).
240
241
R
N
Meter Boot Version 0 to 999,999
View Meter boot loader version. Periods are implied after
2 and 4 decimal digits
(10203 = v01.02.03).
242
243
R
N
Bluetooth Version 0 to 999,999
View Bluetooth module firmware version. Periods are
implied after 2 and 4 decimal digits (10203 = v01.02.03).
244
245
R
N
Gate Drive Version 0 to 999,999
View Gate drive firmware version. Periods are implied
after 2 and 4 decimal digits
(10203 = v01.02.03).
Mod
Bus R/W
RC
Address Name
Choices/Range
Description
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...