INSTALLATION AND SETUP
Programming: Advanced Setup > Motor Protection > System
23
Programming: Advanced Setup > Motor Protection > System
455
RW
N
Underpower Reset 0 - Manual
1 - Automatic
2 - Well Recovery (Submers
-
ible Pump only)
Underpower Reset Method
When set to well recovery, the SubMonitor Connect
infinitely resets an Underpower fault condition based on
the user-selected reset delay.
456
RW
N
Underpower Retry 1 to 10; default = 3
Underpower Automatic Reset Attempts
457
RW
N
Underpower Reset
Delay
1 to 43,200; default = 900
Underpower Reset Delay in seconds
Overpower
menu
458
RW
N
Trip/Alarm
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Choose the type of response for when an Overpower con
-
dition is detected.
459
RW
N
Overpower Level
101 to 200; default = 125
Over Power Level Percentage
460
RW
N
Time to Trip
1 to 120; default = 3
Over Power Delay Time in seconds
461
RW
N
Fault Reset Type
0 - Manual
1 - Automatic (default)
Over Power Reset Method
462
RW
N
Reset Retries
1 to 10; default = 3
Over Power Automatic Reset Attempts
463
RW
N
Reset Delay
1 to 43,200; default = 900
Over Power Reset Delay in seconds
Negative Power
menu
464
RW
N
Trip/Alarm
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
Choose the type of response for when Negative Power is
detected.
Underpower
menu
452
Trip/Alarm
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Choose the type of response for when Underpower is
detected.
453
Underpower Level 101 to 200; default = 125
Underpower Level Percentage
454
Time to Trip
1 to 120; default = 3
Underpower Delay Time in seconds
455
Fault Reset Type
0 - Manual
1 - Automatic (default)
Over Power Reset Method
456
Reset Retries
1 to 10; default = 3
Underpower Automatic Reset Attempts
457
Reset Delay
1 to 43,200; default = 900
Underpower Reset Delay in seconds
Mod
bus
RW
RC
Display Name
Range
Description
Mod
bus
RW
RC
Display Name
Range
Description
Insulation Check
menu
465
RW
N
Trip/Alarm
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
Insulation Check Enable. This measures an approximate
resistance between the W circuit and earth ground.
466
RW
N
Fault Resistance
1 to 2000; default = 500
Insulation Resistance Fault Level
467
RW
N
Alarm Resistance
1 to 3000; default = 1000
Insulation Resistance Alarm Level
SubTemp
menu
468
RW
N
Trip/Alarm
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
SubTemp Motor Protection Enable
469
RW
N
Trip Temp
0 to 150; default = 40
SubTemp Fault Trip Temperature setting in °C
470
RW
N
Alarm Temp
0 to 150; default = 30
SubTemp Alarm Trip Temperature setting in °C
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...