INSTALLATION AND SETUP
Programming: Advanced Setup > Motor Protection > Current
20
404
RW
N
Service Factor
1.0 to 2.0;
1.15 (Surface motor and
Custom default)
1.00 (Submersible motor
default)
multi = 0.01
Motor service factor; refer to the motor nameplate for this
setting.
405
RW
N
Fault Reset Type
0 - Manual
1 - Automatic (default)
Sets the current overload fault reset method.
406
RW
N
Reset Re-tries
1 to 10; default is 3
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
407
RW
N
Reset Delay
0 to 43,200; default = 900
The number of seconds between automatic resets.
408
RW
N
Cooldown
0 - Disabled (default)
1 - Enabled
Turn on or off the overload cool down run prevention fea
-
ture.
409
RW
N
Cooldown Time
1 to 43,200; default = 300
Amount of overload cool down time in seconds
Locked Rotor
Menu
410
RW
N
Trip/Alarm
0 - Off
1 - Fault and Alarm (default)
Choose the type of response for a locked rotor detection.
Stall
Menu
411
Trip/Alarm
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Choose the type of response for motor stall detection.
Overcurrent
Menu
412
RW
N
Trip/Alarm
0 - Off
1 - Fault and Alarm (default)
Choose the type of response for overcurrent detection.
413
RW
N
Current Level
100% to 200%;
default = 110%
Overcurrent threshold to signal a fault in percentage of
nominal current setting.
414
RW
N
Time to Trip
1 s to 120 s; default = 30 s
Amount of time in seconds for the overcurrent situation
to subside. If exceeded, then trigger the fault.
415
RW
N
Fault Reset Type
0 - Manual
1 - Automatic (default)
Sets the overcurrent fault reset method.
416
RW
N
Reset Retries
1 to 10; default = 3
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
417
RW
N
Reset Delay
0 to 43,200; default = 900
The number of seconds between automatic resets.
Current Unbalance
Menu
418
RW
N
Trip/Alarm
0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
Choose the type of response for current unbalance detec
-
tion.
419
RW
N
Unbalance Level
1% to 50%; default = 5%
Percentage of unbalanced current that will trigger a fault
condition.
420
RW
N
Time to Trip
1 s to 120 s; default = 30 s
Amount of time in seconds for the unbalanced current sit
-
uation to subside. If exceeded, then trigger the fault.
421
RW
N
Fault Reset Type
0 - Manual
1 - Automatic (default)
Sets the unbalanced current fault reset method.
422
RW
N
Reset Retries
1 to 10; default = 3
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
423
RW
N
Reset Delay
0 to 43,200; default = 900
The number of seconds between automatic resets.
Mod
bus
RW
RC
Menu / Parameter
Name
Range
Description
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...