COMMUNICATIONS
Modbus RTU Communication
47
500
RW
N
External CT Ratio
0 - NONE (default)
1 - 150:5
2 - 200:5
3 - 250:5
4 - 300:5
5 - 500:5
6 - 600:5
7 - 800:5
8 - 1000:5
Turns Ratio for Installed External CTs
503
RW
N
Contactor
0 - NONE (default)
1 - MRC-9
2 - MRC-12
3 - MRC-18
4 - MRC-22
5 - MRC-32
6 - MRC-40
7 - MRC-50
8 - MRC-65
9 - MRC-75
10 - MRC-85
11 - MRC-100
12 - MRC-130
13 - MRC-150
LS Brand Contactor Model Type
504
R
N
SCR Model
0 - NONE
1 - SKKT 106 (default)
2 - SKKT 172
3 - SKKT 330
4 - SKKT 570
SCR Model
505
RW
N
Pilot Devices
0 - HOA (default)
1 - HOA with Start
2 - Start/Stop
Pilot Device Type
506
RW
Y
Power Fail Return 0 - Off (default)
1 - Last
Return Mode after a Power Failure
507
RW
Y
Shutdown Return 0 - Off (default)
1 - Last
Return Mode after a Shutdown Condition is Cleared
508
RW
N
Soft Start Mode
0 - Linear Ramp (default)
1 - Exponential Ramp
2 - Current Limit
3 - Disabled
Soft Start Mode Setting
509
RW
N
Soft Start Ramp
Time
1 to 30; default = 3
Soft Start Ramp Time in seconds
510
RW
N
Soft Start Voltage
Level
30 to 90; default = 70
Soft Start Voltage Level percentage
511
RW
N
Soft Start Current
Limit
200 to 500; default = 400
Soft Start Current Limit percentage
512
RW
N
Smart Ramp
0 - Disabled
1 - Enabled (default)
This setting enables compensation for unloaded soft starting
motors.
513
RW
N
Soft Stop Mode
0 - Coast to Stop (default)
1 - Linear Ramp
2 - Exponential Ramp
Soft Stop Mode
514
RW
N
Soft Stop Ramp Time 1 to 30; default = 3
Soft Stop Ramp Time
Mod
Bus R/W
RC
Address Name
Choices/Range
Description
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...