DRIVE PROGRAMMING
Default Settings Table - PROT Menu
55
PROT-16 ETH Type
Self Cooled Self Cooled Self Cooled Self Cooled Self Cooled Self Cooled Self Cooled Self Cooled Self Cooled Self Cooled
PROT-17 ETH Delay
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
PROT-18 OH Warn
105 °C
105 °C
105 °C
105 °C
105 °C
105 °C
105 °C
105 °C
105 °C
105 °C
PROT-19 PTC Select
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
Alarm and
Run
PROT-20 PTC Level
50%
50%
50%
50%
50%
50%
50%
50%
50%
50%
PROT-21 OPO Trip
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
PROT-22 OPO Delay
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
PROT-23 OPO Current
1%
1%
1%
1%
1%
1%
1%
1%
1%
1%
PROT-24 OPO Decel
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
PROT-25 LvX Auto Reset
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
PROT-26 IPO Check
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
PROT-27 IPO Ripple
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
By VFD
voltage
PROT-28 IPO Trip
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
Alarm and
Decel
PROT-29 Derating Type
Carrier by
I_T
Carrier by
I_T
Carrier by
I_T
Carrier by
I_T
Carrier by
I_T
Carrier by I_T Carrier by
I_T
Carrier by
I_T
Carrier by
I_T
Carrier by
I_T
PROT-30 PT100 Level 1
5 V
5 V
5 V
5 V
5 V
5 V
5 V
5 V
5 V
5 V
PROT-31 PT100 Level 2
7 V
7 V
7 V
7 V
7 V
7 V
7 V
7 V
7 V
7 V
PROT-32 PT100 L- 1 Freq
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
PROT-33 PT100 L- 1 Delay
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
60 Sec
PROT-34 Ground Fault Lvl
60%
60%
60%
60%
60%
60%
60%
60%
60%
60%
PROT-35 G-Fault Delay
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
PROT-36 STO Alarm Type
STO
Latching
STO
Latching
STO
Latching
STO
Latching
STO
Latching STO Latching
STO
Latching
STO
Latching
STO
Latching STO Latching
PROT-37 IPF S-Search
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
PROT-38 Max IPF Time
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
PROT-39 SS Current Lmt
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
PROT-40 SS After Fault
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
PROT-42 SS Normal Start
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
PROT-43 Spd Search Gain
40%
40%
40%
40%
40%
40%
40%
40%
40%
40%
PROT-44 IPF Restart Dly
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
PROT-45 Fan Control
At power
up
At power
up
At power
up
At power
up
At power
up
At power up
At power
up
At power
up
At power
up
At power up
PROT-46 Last Flt Freq
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-47 Last Flt IGBTT
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-48 Last Flt Cap T
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-49 Last Flt MFI
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-50 Last Flt MFO
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-51 1st Fault
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-52 2nd Fault
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-53 3rd Fault
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-54 4th Fault
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-55 5th Fault
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-56 6th Fault
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only
Read Only
PROT-57 ULD Min Torque
10%
10%
10%
10%
10%
10%
10%
10%
10%
10%
PROT-58 HLD Min Torque
10%
10%
10%
10%
10%
10%
10%
10%
10%
10%
CODE
Display
Basic
Supply Fan
Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
PM Motor
MagForce
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...