OPERATION
Control Options
64
Hand Run Command [SET–10]:
Source of Run Command in Hand mode. VFD starts based on input from:
•
Keypad (Default):
Run command from Start/Stop buttons.
•
Digital Input:
Run command from digital input FWD or REV terminal.
•
RS485:
Run command from RS485 interface. Keypad STOP is disabled.
•
Com Card:
Run command from communications card.
•
Ext HOA in Hand:
Run command from digital input [IO-21~28] set to HAND.
Auto Speed Ref [SET–07]:
Source of Speed Reference in Auto mode. VFD runs at a frequency based on the
following inputs:
•
Keypad:
VFD runs at a fixed frequency set on the Home Screen.
•
Up/Down DI:
Digital input increases or decreases speed when DI terminals [IO-21~28] set to Up and
Down.
•
AVI1 Analog:
Input from external controller, potentiometer, or other device.
•
ACI Analog:
Input from external controller, potentiometer, or other device.
•
AVI2 Analog:
Input from external controller, potentiometer, or other device.
•
RS485 Serial:
Frequency input through Modbus control.
•
COM Card:
Frequency input through communications protocol.
•
PID Output:
VFD speed reference will be provided by PID control based on the difference between
PID
Setpoint [SET–21]
and transducer feedback values.
IMPORTANT:
When PID Mode is selected, additional parameter settings should be verified to ensure
“Standard Operation with PID Feedback Control” on page 66
for more infor
-
mation.
Auto Run Command [SET–08]:
Source of Run Command in Auto mode. VFD starts based on input from:
•
Keypad (Default):
Run command from Start/Stop buttons.
•
Digital Input:
Run command from digital input FWD or REV terminal.
•
RS485:
Run command from RS485 interface. Keypad STOP is disabled.
•
Com Card:
Run command from communications card.
•
Ext HOA in Auto:
Run command from digital input [IO-21~28] set to AUTO.
Forward or Reverse Selection
This feature provides the ability to change the direction of rotation of a motor used in an industrial applica
-
tion. The direction can be set using either the keypad
FWD/REV
button, or by setting the following parameter:
Load Rotation [SET–15]:
Setting this parameter to
FWD & REV
enables the keypad button. Selection of either
FWD Only
or
REV Only
permanently sets the direction and disables the keypad button. This provides protection
to prevent a motor from running in a direction that could damage equipment, such as a pump or fan.
IMPORTANT:
Do not use the Load Rotation setting to correct a motor that is running backwards because of
incorrect wiring.
Jog Feature
The Jog feature provides the ability to activate a motor momentarily. The command can be executed using
either the keypad
F1
button, or switches connected to a digital input.
•
When using the keypad, the motor direction depends on the
Load Rotation [SET–15]
setting. Digital inputs
can be set to either forward or reverse.
•
The jog command cannot be used when the drive is running.
•
When the jog command is active, other run commands are unavailable.
Jog Frequency [VFD–55]:
This sets the speed the motor will run when the jog command is active.
Jog ACC Time [VFD–53]:
This sets the acceleration time from 0 Hz to
[VFD–55]
.
Jog DEC Time [VFD–55]:
This sets the deceleration time from
[VFD–55]
to 0 Hz.
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...