PARAMETER REFERENCE TABLES
Parameter Descriptions > VFD Menu
120
VFD-21 0277 Y ACC-3 Time
0.0 to 600 Sec
Alternate acceleration rate for use with automated Acc/Dec type [ADV-06].
VFD-22 0278 Y DEC-3 Time
0.0 to 600 Sec
Alternate deceleration rate for use with automated Acc/Dec type [ADV-06]
VFD-23 0279 Y ACC-4 Time
0.0 to 600 Sec
Alternate acceleration rate for use with automated Acc/Dec type [ADV-06].
VFD-24 0280 Y DEC-4 Time
0.0 to 600 Sec
Alternate deceleration rate for use with automated Acc/Dec type [ADV-06]
VFD-25 0281 Y S Start Time 1
0.0 to (variable) Sec
S-curve acceleration time leaving initial frequency.
VFD-26 0282 Y S Start Time 2
0.0 to (variable) Sec
S-curve acceleration time approaching next frequency.
VFD-27 0283 Y S End Time 1
0.0 to (variable) Sec
S-curve deceleration time leaving initial frequency.
VFD-28 0284 Y S End Time 2
0.0 to (variable) Sec
S-curve deceleration time approaching next frequency.
VFD-29 0285 N Skip Freq 1 High 0.0 to 599 Hz
Used to bypass mechanical system resonance frequencies. If the received
speed reference is in the skip zone, VFD will run at Low Skip Freq until speed
reference is at or above High Skip Freq. Then, speed will be ramped up
based on acceleration time.
VFD-30 0286 N Skip Freq 1 Low
0.0 to 599 Hz
Low frequency in skip zone 1.
VFD-31 0287 N Skip Freq 2 High 0.0 to 599 Hz
High frequency in skip zone 2.
VFD-32 0288 N Skip Freq 2 Low 0.0 to 599 Hz
Low frequency in skip zone 2.
VFD-33 0289 N Skip Freq 3 High 0.0 to 599 Hz
High frequency in skip zone 3.
VFD-34 0290 N Skip Freq 3 Low 0.0 to 599 Hz
Low frequency in skip zone 3.
VFD-35 0291 N VFD Duty Select 0_Variable Torque
1_Constant Torque
0_Variable Torque (Light Duty)
01_Constant Torque (Normal Duty)
VFD Rated Amps [VFD-47] and Over-Current levels [PROT-07-08] are
affected by this setting.
VFD-36 0292 Y Reset Restart
0_Disable
1_Enable
The VFD will automatically initiate operation once fault is cleared and run
command is received.
VFD-37 0293 Y DC Brake Lvl
0.0 to 100%
Level of DC Brake Current output to the motor during start-up and stopping.
VFD-38 0294 Y DC Time at Run
0.0 to 60 Sec
Duration of the DC Brake current after a run command to apply DC current
to motor to force stop motor for a stable start.
VFD-39 0295 Y DC Time at Stop 0.0 to 60 Sec
Duration of the DC Brake current after a stop command to apply DC current
to the motor inorder to force stop the motor.
VFD-40 0296 Y DC Stop Freq
0.0 to 599 Hz
Frequency when DC Brake will begin during deceleration.
VFD-41 0297 Y Dwell T at Acc
0.0 to 600 Sec
When increasing in frequency to Dwell Frequency at Accel, the duration to
then hold at frequency before continuing to increase frequency.
VFD-42 0297 Y Dwell Hz at Acc
0.0 to 599 Hz
Frequency to hold when increasing in frequency.
VFD-43 0299 Y Dwell T at Dec
0.0 to 600 Sec
When decreasing in frequency to Dwell Frequency at Decel, the duration to
then hold at frequency before continuing to decrease frequency.
VFD-44 0300 Y Dwell Hz at Dec
0.0 to 599 Hz
Frequency to hold when decreasing in frequency.
CODE Mod
Bus AR Display Name
Range
Description
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...