ELECTRICAL INSTALLATION
Power Wiring Connections
40
Frame A:
Power terminals accept wire sizes up to 8 AWG and should be tightened to a torque of 17.4 in-lbs
(1.96 Nm).
Frame B:
Power terminals accept wire sizes up to 4 AWG and should be tightened to a torque of 30.4 in-lbs
(3.43 Nm).
Frame C:
Power terminals accept wire sizes up to 1/0 AWG and should be tightened to a torque of 69.4 in-
lbs (7.84 Nm).
Frame D0:
Power terminals accept wire sizes up to 2/0 AWG and should be tightened to a torque of 69.4 in-
lbs (7.84 Nm).
Frame D:
Power terminals accept wire sizes up to 300 MCM or 4/0 AWG and should be tightened to a
torque of 156 in-lbs (18 Nm).
Frame E:
Power terminals accept wire sizes up to 4/0 AWG*2 and should be tightened to a torque of 174 in-
lbs (20 Nm).
Frame F:
Power terminals accept wire sizes up to 300 MCM*2 or 4/0 AWG*2 and should be tightened to a
torque of 156 in-lbs (18 Nm).
Frame G:
Terminals R, S & T accept wire sizes up to 250 MCM*4 and should be tightened to a torque of 156
in-lbs (18 Nm). Terminals U, V, & T accept wire sizes up to 500 MCM*2 and should be tightened to a torque of
354 in-lbs (40 Nm).
Frame H:
Power terminals accept wire sizes up to 350 MCM*4 and should be tightened to a torque of 156 in-
lbs (18 Nm).