DRIVE PROGRAMMING
Default Settings Table - I/O Menu
52
Default Settings Table - I/O Menu
Parameters in highlighted rows are reset when the application is changed
[SET–00]
.
VFD-33 Skip Freq 3 High
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-34 Skip Freq 3 Low
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-35 VFD Duty Select
Variable
Torque
Variable
Torque
Variable
Torque
Variable
Torque
Variable
Torque
Variable
Torque
Variable
Torque
Constant
Torque
Variable
Torque
Variable
Torque
VFD-36 Reset Restart
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
VFD-37 DC Brake CurLvl
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
VFD-38 DC Time at Run
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
VFD-39 DC Time at Stop
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
VFD-40 DC Stop Freq
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-41
Dwell T at Acc
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
VFD-42 Dwell Hz at Acc
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-43 Dwell T at Dec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
VFD-44 Dwell Hz at Dec
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
VFD-46 ID Code
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only Read Only
VFD-47 VFD Rated Amps
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
By VFD
Rating
VFD-48 Display Select
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
Frequency
Command
VFD-49 Firmware Version Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only Read Only
VFD-50 Disp Filter A
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
VFD-51
Disp Filter KPD
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
VFD-52 FW Date
Read Only Read Only Read Only Read Only Read Only
Read Only
Read Only Read Only Read Only Read Only
VFD-53 Jog ACC Time
20 Sec
20 Sec
20 Sec
20 Sec
20 Sec
2 Sec
20 Sec
20 Sec
20 Sec
2 Sec
VFD-54 Jog DEC Time
30 Sec
30 Sec
30 Sec
30 Sec
30 Sec
2 Sec
30 Sec
30 Sec
30 Sec
2 Sec
VFD-55 JOG Frequency
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
6.0 Hz
VFD-56 Zero-speed Mode
Standby
Standby
Standby
Standby
Standby
Standby
Standby
Standby
Standby
Standby
VFD-57 Power-on Start
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Enable
CODE
Display
Basic
Supply Fan Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
PM Motor
MagForce
CODE
Display
Basic
Supply Fan Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
PM Motor
MagForce
IO-00
ACI Input Sel
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
IO-01
ACI Loss Trip
Decel Stop Decel Stop Decel Stop Decel Stop Decel Stop Decel Stop
Decel Stop Decel Stop Decel Stop Decel Stop
IO-04
ACI Filter T
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
IO-05
AVI1 Input Sel
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
IO-09
AVI1 Filter T
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
IO-10
AVI2 Filter T
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
0.2 Sec
IO-11
PID Filter Time
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
0.5 Sec
IO-12
PID Delay Time
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
IO-13
AI Upper Level
50%
50%
50%
50%
50%
50%
50%
50%
50%
50%
IO-14
AI Lower Level
10%
10%
10%
10%
10%
10%
10%
10%
10%
10%
IO-20
DI Filter
0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec 0.005 Sec
0.005 Sec
0.005 Sec 0.005 Sec 0.005 Sec
0.005 Sec
IO-21
MI1 Define
Speed-L
Speed-L
Speed-L
Speed-L
Speed-L
Speed-L
Speed-L
Speed-L
Speed-L
Speed-L
IO-22
MI2 Define
Speed-M
Speed-M
Speed-M
Speed-M
Speed-M
Speed-M
Speed-M
Speed-M
Speed-M
Speed-M
IO-23
MI3 Define
Speed-H
Speed-H
Speed-H
Speed-H
Speed-H
Speed-H
Speed-H
Speed-H
Speed-H
Speed-H
IO-24
MI4 Define
Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset Fault Reset
IO-25
MI5 Define
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
E-Stop
IO-26
MI6 Define
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
XCEL-L
IO-27
MI7 Define
None
None
None
None
None
None
None
None
None
None
IO-28
MI8 Define
None
None
None
None
None
None
None
None
None
None
IO-29
FO Enable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
IO-30
FO Frequency
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
115 Hz
115 Hz
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...