PARAMETER REFERENCE TABLES
Parameter Descriptions > SET Menu
116
SET-09 0009 N Hand Speed Ref 0_Keypad
1_RS485 Serial
2_AVI1 Analog
3_ACI Analog
4_AVI2 Analog
5_Com Card
Source of speed reference when in Hand mode.
Keypad input.
RS-485 Interface
Analog input from BMS, PLC, Potentiometer or other control device.
Communications card control.
When in Hand mode, PID is disabled.
SET-10 0010 N Hand Run Cmd
0_Keypad
1_Digital Input
2_RS485 Serial
3_Com Card
4_Ext HOA in Hand
Source of Run Command in Hand mode.
Keypad: Run command from Start/Stop button.
Digital Input: Run command from digital input FWD or REV terminal. Key
-
pad STOP is disabled.
RS485 Serial: Run command from RS485 interface. Keypad STOP is dis
-
abled.
Com Card: Run command from communications card. This does not include
CANopen card.
Ext HOA in Hand: Run command from digital input [IO-21~28] set to HOA
HAND (when HOA is in Hand position).
SET-11
0011 Y Accel Time
0 to 600 Sec
Time in seconds for the drive to accelerate from 0 Hz to maximum fre
-
quency. Default depends on Application [SET-00] and VFD HP rating.
SET-12
0012 Y Decel Time
0 to 600 Sec
When Stop Mode is set to Decelerate, time in seconds to slow down from
maximum frequency to 0 Hz. Default depends on Application [SET-00] and
VFD HP rating.
SET-13
0013 Y Low Freq Limit
0.0 to SET-14 (Hz)
The lowest frequency (speed) allowable. If speed control falls below set
-
ting, motor will continue to run at this limit.
SET-14 0014 N High Freq Limit
SET-13 to VFD-00 (Hz)
The highest frequency (speed) allowable. If speed control signal goes
higher, motor will continue to run at this limit.
SET-15
0015 N Load Rotation
0_FWD & REV
1_FWD Only
2_REV Only
Allows the motor to run in the forward and reverse direction. Setting it to a
specific direction prevents injury or damage to equipment.
SET-16 0016 N Stop Mode
0_Decel to stop
1_Coast to stop
Determines how the motor is stopped when a STOP command is initiated.
Decel to stop: VFD decelerates frequency to minimum output frequency
and then stops.
Coast to stop: VFD stops the output instantly and motor free runs until it
comes to a complete standstill.
SET-17
0017 N PID Mode
0_Disable
1_PID Direct
2_PID Inverse
PID control allows the VFD to maintain a process value (pressure, tempera
-
ture etc.) by varying the output frequency based on the difference between
a set point and actual feedback value.
Direct: Output decreases as feedback increases.
Inverted: Output increases as feedback increases.
SET-18
0018 N PID F/B Source
0_ACI
1_AVI1
2_AVI2
Selects an analog input terminal for PID Feedback source.
SET-19 0019 N PID F/B Unit
0_PSI
1_inWC
2_Feet
3_°F
4_CFM
5_GPM
6_%
7_Cust
8_inHg
9_m
10_mBar
11_Bar
12_kPa
13_°C
14_LPM
15_CMH
Measurement unit selection for feedback signal.
SET-20 0020 N PID F/B Max
0.0 to (variable) (Unit)
PID Sensor (Transducer) maximum rating based on transducer range.
SET-21
0021 Y PID Setpoint
0.0 to SET-20 (Unit)
Set the desired value for PID (pressure, temperature, GPM, etc.).
CODE Mod
Bus AR Display Name
Range
Description
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...