PARAMETER REFERENCE TABLES
Parameter Descriptions > I/O Menu
126
IO-56
0568 Y I Hi/Lo Setting
0 to 100%
When any relay is set to (49) At High Current in IO-47~49 and motor cur
-
rent is at or above IO-56 set level (% of FLA), corresponding relay will be
activated.
When any relay is set to (50) At Low Current in IO-47~49 and motor current
is below IO-56 set level (% of FLA), corresponding relay will be activated
IO-57
0569 Y FDT-4/5 Setting 0.0 to 60 Hz
Frequency setting for FDT-4 and FDT-5 functions.
IO-58
0570 Y Relay NO/NC
Sets the relay outputs numbered in hex format to either N.O. or N.C. config
-
uration. The configuration is in binary format Bit0, Bit1, Bit2, etc. corre
-
sponding to RA1, RA2, etc. from right to left. Empty box indicates that Relay
is N.O. and solid box that it is N.C. Example below shows solid box (N.C.
contact configuration) for Bit0 DO (RA1). The physical N.O. contact of RA1
relay is always closed (relay is activated) until the selected function in IO-
47~49 is activated, then contact will be open.
IO-59
0571 Y AFM1 Out Select 0_Output FREQ
1_Output AMP (rms)
2_Output voltage
3_DC Bus voltage
4_Power Factor
5_Power
6_AVI1 %
7_ACI %
8_AVI2 %
9_Constant Output
Defines functionality of Analog Output 1 (AFM1).
IO-60
0572 Y AFM1 Gain
0 to 500%
Adjusts the analog voltage level output of AFM1.
IO-61
0573 Y AFM2 Out Select See [IO-59]
Defines functionality of Analog Output 2 (AFM2).
IO-62
0574 Y AFM2 Gain
0 to 500%
Adjusts the analog voltage level output of AFM2.
IO-63
0575 Y AFM1 mA Select 0_0-20mA output
1_4-20mA output
Selects current range of AFM1 output.
IO-64
0576 Y AFM2 mA Select 0_0-20mA output
1_4-20mA output
Selects current range of AFM2 output.
IO-65
0577 Y AFM1 Filter Time 0 to 20 Sec
Noise filtering of AFM1 output.
IO-66
0578 Y AFM2 Filter Time 0 to 20 Sec
Noise filtering of AFM2 output.
IO-67
0579 Y MO by AI Level
0_AVI1
1_ACI
2_AVI2
When input signal selected is higher than AI Upper Level [IO-13], then MO
becomes active. Once input signal decreases below AI Lower Level [IO-14],
then MO becomes inactive.
CODE Mod
Bus AR Display Name
Range
Description
Hz
Freq Command
FDT-4 MO
Time
FDT-4/5 setting
FDT-5 MO
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...