Goodrive20 Series VFD
Function parameter list
-77-
Function
code
Name
Description
Default
Modify
sudden jump frequency (
P08.16
), that is,
the value that the sudden jump frequency
corresponds to the wobbling frequency
when the VFD runs at the wobbling
frequency.
Rise time of wobbling frequency: Time
needed for the VFD to run from the lowest
point to the highest one.
Fall time of wobbling frequency: The time
needed for the VFD to from the highest
point to the lowest one.
Setting range of
P08.15
: 0.0
–100.0%
(relative to the set frequency)
Setting range of
P08.16
: 0.0
–50.0%
(relative to the amplitude of wobbling
frequency)
Setting range of
P08.17
and
P08.18
:
0.1
–3600.0s
P08.19
Number of
decimal
places of
linear
speed/freque
ncy
Ones place: Linear speed displays
number of decimal places
0: No decimal place
1: One
2: Two
3: Three
Tens place: Frequency displays number of
decimal places
0: Two
1: One
0x00
○
P08.20
Analog
calibration
function
0: Disable
1: Enable
1
◎
P08.21
DEC time of
emergency
stop
0.0
–6553.5 s
0.0 indicates coast to stop.
0.0s
○
P08.22
Delay to enter
the sleep
state
0.0
–3600.0s
It indicates the delay to enter the sleep
state, and it is valid only when ones place
of P01.19 is set to 2.
2.0s
○