Goodrive20 Series VFD
Function parameter list
-39-
Function
code
Name
Description
Default Modify
P01.04
Braking
time before
start
time is set to 0, the DC braking is invalid.
Stronger braking current indicates larger
braking power. The DC braking current
before start is the percentage of rated
current of the VFD.
Setting range of
P01.03
: 0.0
–100.0% (rated
current peak of the VFD)
Setting range of
P01.04
: 0.00
–50.00s
0.00s
◎
P01.05
ACC and
DEC mode
The function code indicates that the
changing mode of the frequency during start
and running.
0: Linear type. The output frequency
increases or decreases linearly.
fmax
Output frequency f
t1
t2
Time t
1: S curve. The output frequency increases
or decreases according to the S curve
Output frequency f
Time t
t1
t2
t1
t2
t1=P01.06
t2=P01.07
The S curve is generally applied to elevator,
conveyors, and other application scenarios
where smoother start or stop is required.
0
◎
P01.06
ACC time
of the
starting
step of S
curve
Setting range: 0.0
–50.0s
Note:
Valid when
P01.05
is 1.
0.1s
◎
P01.07
DEC time
of the
0.1s
◎