Goodrive20 Series VFD
Communication protocol
-135-
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
Input IO
300BH
000
–1FF
AI 1
300CH
Range: 0.00
–10.00V
R
AI 2
300DH
Range: 0.00
–10.00V
R
AI 3
300EH
Range: 0.00
–10.00V
R
AI 4
300FH
Range: -10.00
–10.00V
R
Read high speed
pulse 1 input
3010H
Range: 0.00
–50.00kHz
R
Read high speed
pulse 2 input
3011H
Reserved
R
Read current
step of the
multi-step speed
3012H
Range: 0
–15
R
External length
3013H
Range: 0
–65535
R
External
counting value
3014H
Range: 0
–65535
R
Torque setting
3015H
-300.0
–300.0% (Unit: 0.1%)
R
VFD code
3016H
R
Fault code
5000H
R
R/W characteristics means the function is with read and write characteristics. For example,
"communication control command" is writing chrematistics and control the VFD with writing
command (06H). R characteristic can only read other than write and W characteristic can only
write other than read.
Note:
when operating on the VFD with the table above, it is necessary to enable some
parameters. For example, the operation of running and stopping, it is necessary to set
P00.01
to communication running command channel. And when operate on "PID given", it is
necessary to set
P09.00
to "Modbus communication setting"."
The encoding rules for device codes (corresponding to identifying code 2103H of the VFD
MSB of code
Meaning
LSB of code
Meaning
01
Goodrive
06
Goodrive20 Vector VFD
Note:
The code is consisted of 16 bit which is high 8 bits and low 8 bits. High 8 bits mean the motor
type series and low 8 bits mean the derived motor types of the series.
7.4.3 Fieldbus ratio values
The communication data is expressed by hex in actual application and there is no radix point
in hex. For example, 50.12Hz cannot be expressed by hex so 50.12 can be magnified by 100