Goodrive20 Series VFD
Function parameter list
-49-
Function
code
Name
Description
Default Modify
P03.10
Current
loop
integral
coefficient I
codes.
The parameters P03.09 and P03.10 are
applicable only to SVC 0 (
P00.00
=0).
Setting range: 0
–65535
1000
○
P03.11
Torque
setting
method
The function code is used to enable the
torque control mode, and set the torque
setting method.
0: Torque control is invalid
1: Keypad setting torque (
P03.12
)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDI
6: Multi-step torque
7: Modbus communication
8
–10: Reserved
Note
:
Setting
methods
2
–7,
100%
corresponds to 3 times of the rated motor
current.
0
○
P03.12
Torque set
through
keypad
Setting range: -300.0%
–300.0% (of the rated
motor current)
50.0%
○
P03.13
Torque
reference
filter time
0.000
–10.000s
0.100s
○
P03.14
Setting
source of
forward
rotation
upper-limit
frequency
in torque
control
0: Keypad (
P03.16
sets the value when
P03.14
=1;
P03.17
sets the value when
P03.15
=1)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDI
5: Multi-step setting
6: Modbus communication
7
–9: Reserved
Note:
Setting
methods
1
–9,
100%
corresponds to the maximum frequency.
0
○
P03.15
Setting
source of
reverse
rotation
upper-limit
0
○