Goodrive20 Series VFD
Function parameter list
-42-
Function
code
Name
Description
Default Modify
Setting range: 0.00
–100.00s (valid only
when
P01.16
=1)
P01.18
Terminal-b
ased
running
command
protection
at power-on
When the channel of running commands is
terminal control, the system detects the state
of the running terminal during power-on.
0: The terminal running command is invalid
at power-on. Even the running command is
considered as valid during power-on, the
VFD does not run and it keeps the protection
state until the running command is canceled
and enabled again.
1: The terminal running command is valid at
power-on. If the running command is
considered as valid during power-on, the
VFD is started automatically after the
initialization.
Note:
Exercise caution before using this
function. Otherwise, serious result may
follow.
0
○
P01.19
Action
selected
when
running
frequency
less than
frequency
lower limit
(valid when
frequency
lower limit
greater
than 0)
0x00
–0x12
Ones place:
0: Run at the frequency lower limit
1: Stop
2: Sleep
Tens place:
Stop mode
0: Coast to stop
1: Decelerate to stop
0x00
◎
P01.20
Wake-up-fr
om-sleep
delay
This
function
code
determines
the
wake-up-from-sleep delay time. When the
running frequency of the VFD is lower than
the lower limit, the VFD becomes standby.
When the set frequency exceeds the lower
limit one again and it lasts for the time set by
P01.20
, the VFD runs automatically.
0.0s
○