Goodrive20 Series VFD
Function parameter list
-37-
Function
code
Name
Description
Default Modify
P00.16
AVR
function
selection
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can
cancel the impact on the output voltage of
the VFD because of the bus voltage
fluctuation.
1
○
P00.18
Function
parameter
restore
0
–6
0: No operation
1: Restore the default value (excluding the
motor parameters)
2: Clear fault records
3: Function code locking (lock all function
codes)
4: Reserved
5: Restore the default value (factory test
mode)
6: Restore the default value (including the
motor parameters)
Note:
After the selected operation is performed,
the
function
code
is
automatically
restored to 0. Restoring default values
may delete the user password. Exercise
caution when using this function.
Restoring default values (factory test
mode) will restore the parameters to the
corresponding
standard
version.
Non-professionals shall exercise caution
when using this function.
0
◎
P01 group Start and stop control
Function
code
Name
Description
Default Modify
P01.00
Start mode
0: Direct start: start from the starting
frequency
P01.01
1: Start after DC braking: start the motor from
the starting frequency after DC braking (set
the parameter
P01.03
and
P01.04
). It is
suitable in the cases where reverse rotation
0
◎