Goodrive20 Series VFD
Function parameter list
-54-
Function
code
Name
Description
Default
Modify
Output voltage
Output
frequency
Cut-off
boost
b
Setting range of
P04.01
: 0.0%: (automatic)
0.1%
–10.0%
Setting range of
P04.02
: 0.0%
–50.0%
P04.03
V/F
frequency
point 1
When P04.00 =1 (multi-dot V/F curve), you
can
set
the
V//F
curve
through
P04.03
–P04.08.
Output voltage
Output
frequency
(Hz)
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
The V/F curve is generally set according to
the load characteristics of the motor.
Note:
V1
<
V2
<
V3, f1
<
f2
<
f3. Too high
voltage for low frequency will cause motor
overheat or damage and cause VFD
overcurrent stall or overcurrent protection.
Setting range of
P04.03
: 0.00Hz
–P04.05
Setting range of
P04.04
,
P04.06
and
P04.08
:
0.0%
–110.0% (of the rated motor voltage)
Setting range of
P04.05
:
P04.03
–
P04.07
Setting range of
P04.07
:
P04.05
–
P02.02
(of
the rated motor frequency)
0.00Hz
○
P04.04
V/F
voltage
point 1
0.0%
○
P04.05
V/F
frequency
point 2
0.00Hz
○
P04.06
V/F
voltage
point 2
0.0%
○
P04.07
V/F
frequency
point 3
0.00Hz
○
P04.08
V/F
voltage
point 3
0.0%
○
P04.09
V/F slip
compensati
on gain
This function code is used to compensate for
the motor rotating speed change caused by
load change in SVPWM control mode, and
thus improve the mechanical characteristics
of the motor. You need to calculate the rated
slip frequency of the motor as follows:
△
f= f
b
-nxp/60
100.0%
○